| Plan Review Notes For Permit 07040663 |
| Permit Number |
07040663 |
|
| Review Stop |
I |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-26 12:06:47 | | | | | | | DENIED/INCOMPLETE INFORMATION. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PROVIDE FEEDER CONDUIT AND CONDUCTOR SIZES,TYPES | | | AND OCP. INDICATE THE LOCATION OF THE HOUE PANEL AND | | | FEEDER ROUTE ON THE SITE PLAN. | | | | | | 2} PROVIDE A CALCULATION FOR THE FOR THE LOAD(S) | | | SERVED. SEE ARTICLE 555.12 NEC. | | | | | | 3} A DISCONNECTING MEANS PER 225.31 SHALL BE LOCATED | | | PER 555.7.PLEASE INDICATE INTENDED LOCATION ON THE | | | PLAN. | | | | | | 4} PLEASE PROVIDE SPECIFICATIONS FOR THE SHORE POWER | | | RECEPTACLE EQUIPMENT TO BE INSTALLED ON THE DOCK. | | | | | | 5} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | | FAC. | | | | | | 6} THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE TOTAL COST OF LABOR AND | | | MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF | | | NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES PER 108.3 FBC AS | | | AMENDED. INCREASE THE VALUE AT THE | | | COUNTER WHEN RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | 2007-04-20 15:24:11 | TO "E" BOX |
|