| Date |
Text |
| 2008-02-15 08:52:09 | 2008-02-15 08:52:09 |
| | |
| | *** DENIEDREVISIONS*** |
| | |
| | 1) NOTE: PLEASE SEE AS REQUESTED ON ALL PREVIOUS |
| | REVIEWS. PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS FOR |
| | EGRESS PATHS FOR STAIRS UNDER NORMAL AND EMERGENCY |
| | CONDITIONS PER LS 1017.8.1.3 AND 7.9.2.2. |
| | THE ONLY SUBMITTED LEVELS ARE THE LEVELS UNDER |
| | EMERGENCY WHICH ARE OK, HOWEVER NO LEVELS UNDER NORMAL. |
| | THE NORMAL LIGHTING LEVELS FOR STAIRS IS TEN FOLD WHAT |
| | IS REQUIRED AS A MINIMUM UNDER EMERGENCY. |
| | ONCE AGAIN, PLEASE SEE 7.8.1.3 WHICH REQUIRES * 10FT |
| | CANDLES MINIMUM. THE FOLLOWING IS TEXT WHICH HAS BEEN |
| | CUT AND PASTED DIRECTLY FROM NFPA-101 2003. |
| | *** |
| | 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN |
| | AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND |
| | EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE |
| | ILLUMINATED AS FOLLOWS: |
| | (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM |
| | ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX |
| | (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. |
| | |
| | PLEASE SUBMIT |
| | |
| | 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY |
| | OR EXIT LIGHTS. THERE ARE EXCEPTIONS HOWEVER BASED ON |
| | THE LIGHTING AND CIRCUITING ON PLANS THE EXIT LIGHTS IN |
| | MAIN ENTRANCE AREA NEED TO BE CIRCUITED AHEAD OF ANY |
| | SWITCHING OR CONTROL DEVICES AND TO LOCAL BRANCH |
| | CIRCUIT. |
| | PLEASE THERE IS THE OCTAGONAL NOTE #1 ON THE NHP-8 |
| | CIRCUIT IN MAIN LOBBY, HOWEVER OCTAGONAL NOTE #1 SHOWS |
| | THIS AS *NOT USED*. |
| | PLEASE COORDINATE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE. SHEETS EE-001, EP-101, EP-102 |
| | AND EC-102 APPEAR TO BE OK AT THIS TIME. THE OTHER |
| | SHEETS SUCH AS RISER SHEET WHICH SHOWS LOADS AND PANEL |
| | SCHEDULES WILL BE GETTING REVISED BASED ON NOTES |
| | ABOVE. |
| | REDLINED NEC 517.1 AS THIS APPLIES TO OCCUPANCY AND |
| | SCOPE OF WORK. |
| | ONLY SHEETS NOTED AS EE-001, EP-101, EP-102 AND EC-102 |
| | ARE BEING STAMPED. ONE COPY OF THESE SHEETS ARE REMOVED |
| | FROM ONE SET AND KEPT FOR FILE SET OF PLANS. ONE SET OF |
| | SHEETS ARE GIVEN BACK FOR THE CONTRACTORS ON-SITE SET. |
| | |
| | ** IF THERE ARE QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-02-14 19:38:48 | 2008-02-14 19:38:49 |
| | |
| | NOTES TO FOLLOW ONCE COMPLETED. SOME SHEETS ARE OK, |
| | SOME REMAIN WITH COMMENTS. |
| 2008-02-14 19:27:50 | 2008-02-14 19:27:50 |
| | |
| | IN ELEC FOR REVIEW, PLANS CONTAINS REVISIONS FOR FIRE, |
| | MECH, BLDG ALSO NOT ONLY ELECTRICAL AS INDICATED ON |
| | COVER SHEET. |