| 2007-12-23 11:37:35 | 2007-12-23 11:37:35 |
| | ** DENIED4TH ** |
| | |
| | ** PLANS CONTAIN SOME ITEMS WHICH MAY BE REDLINED AND |
| | WILL NEED TO BE REVISED BEFORE ROUGH HOWEVER PLEASE SEE |
| | SOME ITEMS BELOW WHICH MUST BE DONE AT THIS TIME. THE |
| | NOTES WITH ** MUST BE ADDRESSED AT THIS TIME. THE NOTES |
| | WITHOUT ** WILL STILL NEED TO BE ADDRESSED, HOWEVER MAY |
| | BE DONE AT THIS TIME OR BEFORE ROUGH. |
| | |
| | |
| | ** 1) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS |
| | LIGHTING PERFORMANCE DONE UNDER TABLE *B* FOR SPACE BY |
| | SPACE HOWEVER THERE ARE ALSO SHEETS FOR FORM 400C? |
| | PLEASE KNOW THAT IN EITHER CASE, THE SEPARATE LIGHTING |
| | PERFORMANCE CALCULATIONS SUBMITTED EACH MUST CONTAIN A |
| | COMPLETED TITLE BLOCK FROM THE DESIGN FIRM/ENGINEER OF |
| | RECORD ALONG WITH EACH SHEET SIGNED, DATED AND SEALED. |
| | PLEASE SEE FAC 61G15-23.002, FS 471.023. |
| | PLEASE KNOW THESE MAY BE SENT AND PLACED WITH PLANS AS |
| | THE CALCULATIONS ARE OK. |
| | AS NEW FORM 400C IS NOW BEING SUBMITTED FOR THE FIRST |
| | TIME, MECHANICAL REVIEW WILL BE REQUIRED EVEN AS THIS |
| | WAS PREVIOUSLY PASSED. |
| | |
| | 2) NOTE: PLEASE CLARIFY WHERE THE MAXIMUM TIMES ON |
| | OCCUPANCY SENSORS ARE? |
| | PLEASE CLARIFY TYPE OF OCCUPANCY DEVICE. IR? ETC |
| | 13-415.1.ABC.1.1, .1.2 |
| | PLEASE SEE MISSING DEVICE FROM ROOM 159. |
| | |
| | ** 3) NOTE: PLEASE CLARIFY THE NEW UPS WHICH HAS NOW |
| | BEEN ADDED TO PLANS WHICH WAS NOT ON PREVIOUS PLANS. |
| | THE RESPONSE LETTER MENTIONS THE FIXTURES WOULD NOT |
| | PROVIDE THE OUTPUT FOR MINIMUM LIGHTING LEVELS, HOWEVER |
| | AS MENTIONED ON ALL PREVIOUS REVIEWS THE LIGHTING |
| | LEVELS UNDER NORMAL FOR STAIRS IS 10FT CANDLES PER |
| | 7.8.1.3 AND IS PERMITTED TO GO DOWN TO 1FT CANDLE UNDER |
| | EMERGENCY CONDITIONS PER 7.9.2.2. THE AVERAGE FT CANDLE |
| | LEVELS UNDER EMERGENCY ARE NOT SHOWN HOWEVER BASED ON |
| | THE NUMBER OF POINTS AND THE LEVELS SHOWN IT SEEMS |
| | PERHAPS PREVIOUS NOTES WERE NOT TYPED IN A MANOR WHICH |
| | WAS UNDERSTOOD. |
| | PLEASE CLARIFY RESPONSE AND LIGHTING LEVELS BEING |
| | SHOWN. PLEASE SEE THE |
| | REAR STAIR ON PLANS CONTAIN A NOTE WHICH MENTIONS TO |
| | PLACE ON LOBBY 100 NHP-6 CIRCUIT YET THIS SAME REAR |
| | STAIR HAS A NOTE TO CIRCUIT LIGHTS TO NHP-8. HOW WILL |
| | THIS WORK AS THIS PLACES 220/240V ON FIXTURES. THIS |
| | MUST BE A MISPRINT. |
| | PLEASE SEE THE PANEL SCHEDULE DOES NOT INDICATE ANY |
| | CIRCUITING TO THE UPS AND SHOWS CIRCUITS TO FIXTURE |
| | UNITS. |
| | PLEASE CALL TO GO OVER THIS FOR LIGHTING. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |