| Plan Review Notes For Permit 07040621 |
| Permit Number |
07040621 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-11-26 11:16:21 | *****PROVISO***** | | | | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | | THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN | | | REVIEWS HAS BEEN ADDRESSED: | | | | | | | | | 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION | | | 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT | | | ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC | | | PLEASE ADDRESS/INDICATE COMMENT IN THE PLANS AND/OR | | | SPECIFICATIONS | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|