| | *** DENIED 2ND REVIEW *** |
| | |
| | PALM HEALTH CARE |
| | PHASE 3 INTERIOR BUILD OUT. |
| | |
| | |
| | ** PLEASE SEE THERE NOTES FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | COMMENTS BASED ON INFORMATION NOW PLACED ON PLANS OR |
| | INFORMATION NOW SUBMITTED WHICH WAS NOT ON PREVIOUS |
| | PLANS. |
| | |
| | ** THERE ARE STILL ITEMS WHICH WERE NOT SUBMITTED; |
| | THEREFORE A REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE. |
| | WHEN INFORMATION PREVIOUSLY REQUESTED IS NOT SUBMITTED |
| | AND A REVIEW OF THOSE ITEMS CAN NOT BE DONE, THEN MORE |
| | OFTEN THAN NOT THERE ARE NEW COMMENTS TWO, THREE OR |
| | FOUR REVIEWS LATER AS THE INFORMATION WAS NEVER |
| | SUBMITTED FOR REVIEW. PLEASE SEE NOTES BELOW. (#3) |
| | |
| | |
| | 1) NOTE:THIS NOTE WILL REMAIN FROM PREVIOUS REVIEW AS |
| | THE SHELL PLANS HAVE NOT YET BEEN PERMITTED AND CHANGES |
| | WILL BE FORTH COMING BASED ON COMMENTS FROM THIS REVIEW |
| | AND PREVIOUS REVIEW ON SHELL PERMIT REVIEW. |
| | PLEASE KNOW THAT IT IS MOST IMPORTANT TO COORDINATE |
| | PLANS WITH THE PLANS WHICH WERE SUBMITTED FOR SHELL |
| | BUILDING AND ADDITION. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 2) NOTE:PLEASE SEE THIS IS THE 2ND REQUEST: PLEASE |
| | SEE THE ENERGY CALCULATIONS SUBMITTED FOR THE BUILD OUT |
| | OF SPACE. |
| | PLEASE SEE THAT THE RESPONSE LETTER MENTIONS THESE WILL |
| | BE SUBMITTED AND DONE HOWEVER PLEASE SUBMIT *TWO* |
| | COMPLETE SETS OF ENERGY CALCULATIONS, SIGNED DATED AND |
| | SEALED BY THE RESPONSIBLE DESIGNER(S) OF RECORD AS |
| | REQUIRED PER FBC 13-103.1.1.1 , FAC 61G15-23.002, FS |
| | 471.025, 481.221. |
| | |
| | PLEASE KNOW THAT BASED ON THE BUILD OUT BEING SUBMITTED |
| | FOR PERMIT, THE KNOWN ENERGY CONSUMPTION ETC AND METHOD |
| | FOR SHELL PERMIT WOULD CHANGE. |
| | PLEASE BE SURE TO COORDINATE ALL FIXTURES, FIXTURE |
| | WATTAGES, TYPE OF FIXTURES, CONTROLS AND NUMBER OF |
| | FIXTURES BETWEEN PLANS AND ENERGY CALCULATIONS. AS THE |
| | CONTROLS AND AREAS ON THE PLANS MAY CHANGE THIS MAY |
| | AFFECT THE CALCULATIONS. . |
| | PLEASE SEE ELECTRIC TYPE WATER HEATERS FOR EXAMPLE ARE |
| | BEING SHOWN ON THE IDR, YET THE PLANS DO NOT SHOW |
| | THIS? |
| | PLEASE SUBMIT AND SHOW DETAILED CODE COMPLIANCE FOR |
| | LIGHTING CONTROLS AS REQUIRED PER CHAPTER 13 OF THE |
| | 2004 FBC. PLEASE SEE THAT SOME REFERENCES TO A LIGHTING |
| | CONTROL PANEL IS BEING NOTED HOWEVER THERE ARE TOO MANY |
| | AREAS WHICH ARE MISSING THE REQUIRED OVER RIDES FOR |
| | SPACES AND ZONES. PLEASE KNOW THAT ONE LIGHTING CONTROL |
| | PANEL MAY NOT FEED TWO FLOORS AS THE LCP SUBMITTED |
| | INDICATES. |
| | |
| | PLEASE SEE THE ELECTRICAL LIGHTING PLANS SUBMITTED ARE |
| | NOT COMPLETE WITH LIGHTING CONTROLS NOT ONLY REQUIRED |
| | PER CHAPTER 13, BUT MANY ROOMS AND AREAS DO NOT |
| | INDICATE ANY CONTROL FOR LIGHTING AT ALL. SOME |
| | LOCATIONS SHOWS A SYMBOL FOR A SWITCH HOWEVER MOST DO |
| | NOT SHOW ANY DEVICES |
| | PLEASE KNOW THAT STATING ONE NOTE (#5) WHICH MENTIONS |
| | OCCUPANCY DEVICE REQUIRED, DOES NOT SHOW CODE |
| | COMPLIANCE. |
| | PLEASE SHOW SCHEDULE IF A SYSTEM IS DESIGNED, OR |
| | INSTALLED. PLEASE INDICATE ALL MAXIMUM TIMES ON OVER |
| | RIDE DEVICES; PLEASE SHOW ALL DEVICES ON PLANS SO THAT |
| | COVERAGE FOR CODE COMPLIANCE AND SPACE CONTROLS CAN BE |
| | REVIEWED. |
| | 13-415.1.ABC.1.1, .1.2, .1.3. 13-415.1.AB.1.1, |
| | 13-415.2 |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| | BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. |
| | THE VD FOR FEEDERS WERE LOCATED ON THE RISER HOWEVER |
| | PLEASE CLARIFY WHERE THE WORST CASE FOR BRANCH |
| | CIRCUIT(S) ARE SHOWN. |
| | THIS INFORMATION IS REQUIRED TO BE SIGNED, DATED AND |
| | SEALED BY THE RESPONSIBLE DESIGN PROFESSIONAL ALONG |
| | WITH TITLE BLOCK INFORMATION ON PLANS AND SHEETS. |
| | 13-103.1.1.1 |
| | |
| | ** PLEASE KNOW AT THIS TIME PLANS DO NOT INDICATE |
| | COMPLIANCE WITH THE 2004 FBC CHAPTER 13 AND MANY ITEMS |
| | REQUIRED FOR REVIEW ARE MISSING. PLEASE KNOW THERE MAY |
| | BE NEW COMMENTS ON THE FOLLOWING REVIEW AS INFORMATION |
| | WAS NOT SUBMITTED. |
| | PLEASE SEE CHAPTER 13 IN THE 2004 FBC . |
| | |
| | 3) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED |
| | PHOTO-METRICS. SOME OF THESE WERE ADDED HOWEVER NEED |
| | LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS. FLORIDA |
| | ADMINISTRATIVE CODE 61G15-33.004 |
| | ** PREVIOUS REVIEW NOTE: PLEASE SEE THAT THE PLANS ARE |
| | MISSING THE REQUIRED EGRESS PHOTO-METRICS AS PREVIOUSLY |
| | REQUESTED ON SHELL/ADDITION PLANS. AS THE |
| | SHELL/ADDITION PLANS ARE NOT ISSUED AT THIS TIME AND DO |
| | NOT INDICATE COMPLIANCE, PLEASE SUBMIT THE REQUIRED PER |
| | NFPA-101 7.8.1.3, 7.9.2.2 |
| | PLEASE ALSO SEE THE MULTI-USE BATHROOMS WILL BE |
| | REQUIRED TO CONTAIN A BATTERY BACK UP FIXTURE OF SOME |
| | TYPE. |
| | PLEASE SEE NOTES UNDER MAIN BUILDING SHELL/ADDITION |
| | PERMIT. |
| | |
| | 4) NOTE:PLEASE SEE THE RISER HAS NOW BEEN COMPLETELY |
| | CHANGED AND REVISED AND HAD CREATED SOME NEW COMMENTS. |
| | THERE ARE ALSO SOME COMMENTS WHICH STILL REMAIN FROM |
| | PREVIOUS REVIEW. |
| | PLEASE SEE THE RISER NOW SHOWS TWO NEW 400AMP MAINS |
| | FROM THE SUPPOSED EXISTING GUTTER FEEDING A NEW GUTTER. |
| | NO INFORMATION FOR THESE MAINS WAS SUBMITTED. NO TAP |
| | CONDUCTOR SIZES FROM THE EXISTING GUTTER, NOT |
| | CONDUCTORS FROM THE MAINS TO THE NEW GUTTER. (240.21, |
| | 240.4, 310.16) PLEASE VERIFY THE RISER AS THIS SHOWS NO |
| | METERING DEVICES ON THESE TWO MAINS. PLEASE OBTAIN |
| | INFORMATION FROM FPL. |
| | PREVIOUS NOTE # 5 REQUESTED THE RISER TO BE COMPLETE |
| | FOR ALL INFORMATION. |
| | |
| | 5) NOTE: PLEASE SEE AIC RATINGS ARE NOT SUBMITTED FOR |
| | ALL EQUIPMENT AS REQUESTED ON THE PREVIOUS REVIEW. |
| | STATING THE AVAILABLE FAULT CURRENT AT MOST LOCATIONS |
| | ON THE RISER IS FINE HOWEVER THIS DOES NOT GIVE THE |
| | INFORMATION FOR THE REQUIRED MINIMUM RATINGS FOR |
| | EQUIPMENT. |
| | 110.9 |
| | FBC 106.3.5.1.2 |
| | **REQUESTED ON PREVIOUS REVIEW NOTE # 5 |
| | |
| | 6) NOTE: PLEASE SEE THE RISER NOW SHOWS THE *GROUNDING |
| | ELECTRODE CONDUCTOR* AFTER THE FIRST MEANS OF |
| | DISCONNECT WHICH IS NOT PERMITTED AND NOT INSTALLED AS |
| | THE CODE REQUIRES PER 250.6, 250.24, 250.50 ETC. PLEASE |
| | SEE THIS WAS REQUESTED ON THE PREVIOUS REVIEW NOTE #5 |
| | |
| | 7) NOTE: PLEASE SEE MISSING *EQUIPMENT GROUNDING |
| | CONDUCTORS AFTER THE FIRST MEANS OF DISCONNECT AS |
| | REQUIRED PER 250.110, 250.24, 250.122. |
| | |
| | 8) NOTE: PLEASE SEE THE RISER IS STILL IN QUESTION AS |
| | SHOWN AS THE RISER NOW CONTAINS TWO 400AMP MAINS AND A |
| | 800AMP MAIN ON SERVICE ENTRANCE CONDUCTORS RATED AT |
| | 950AMPS. |
| | THE SERVICE CALCULATIONS SUBMITTED ARE BASED ON SOME |
| | AREAS AS SHELL AND NOT CLEAR ON THE COMPLETE SCOPE AND |
| | LOADS AND WHY 1600AMPS WORTH OF MAINS ARE BEING PLACED |
| | ON A SERVICE ONLY RATED AT 975AMPS BASED ON THE |
| | CONDUCTORS. |
| | THE RISER IS ALSO STILL IN QUESTION AS BASED ON THE |
| | TOTAL AMOUNT OF METER AND MAIN DISCONNECTS SHOWN. THE |
| | RISER LENDS TO TWO TENANTS ON THE FIRST FLOOR HOWEVER |
| | THE BUILD OUT PLANS ONLY INDICATE ONE TENANT. IF THIS |
| | IS INDEED ONE TENANT AND OCCUPANT, ONLY ONE METER IS |
| | PERMITTED. |
| | PLEASE ALSO SEE THE RISER LENDS TO THREE POSSIBLE |
| | TENANTS UPSTAIRS, YET THE PLANS ONLY LEND TO TWO. THE |
| | AMOUNT OF METERS PERMITTED TO EACH TENANT IS ONE. |
| | (HOUSE IS NIC) |
| | THIS INFORMATION WILL BE SENT TO ZONING AND BUILDING |
| | BASED ON OCCUPANCY AND TENANT SEPARATIONS ETC. PLEASE |
| | CLEAR UP RISER AND PROVIDE INFORMATION FOR THIS AS |
| | SHOWN. |
| | 215.5, 230.70, 230 ETC |
| | 90.4 |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION |
| | NEEDED. |
| | |
| | 9) NOTE:THIS IS FROM PREVIOUS REVIEW NOTE #9. PLEASE |
| | SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE THE |
| | MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA REQUIRED |
| | AREAS. DEVICES ARE BEING SHOWN ON PLANS/LEGEND. PLEASE |
| | CORRELATE WITH PLANS, AND FA SHEETS SUBMITTED. |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| | SETS. |
| | FBC 106.3.5.1.2 |
| | ** THE RESPONSE MENTIONS TO SEE THE HORNS ARE SET AT |
| | 1WATT AND CD LEVELS AT 15CD. THE RESPONSE LETTER |
| | SPECIFICALLY STATES TO SEE *EC 001* HOWEVER PLEASE SEE |
| | THE PLANS SUBMITTED CONTAIN A EE-001 AND EC-301 HOWEVER |
| | NO EC-001. IN EITHER CASE THESE MINIMUM LEVELS COULD |
| | NOT BE LOCATED ON THESE SHEETS. |
| | THE LEVELS ARE SUBSTANTIALLY HIGHER THAN THAT OF |
| | NFPA-72 |
| | |
| | 10) NOTE:SAME AS PREVIOUS REVIEW NOTE #10: PLEASE |
| | KNOW THAT THE LOW VOLTAGE SECURITY PLANS FOR CAMERAS |
| | ETC ARE TO BE UNDER SEPARATE PERMITS. |
| | THE RESPONSE LETTER SPECIFICALLY STATES THAT THIS IS |
| | NOT PART OF THE PACKAGE, HOWEVER PLEASE CLARIFY HOW AND |
| | WHY THESE PLANS ARE STILL BEING SUBMITTED. |
| | |
| | 11) NOTE: PREVIOUS NOTE #11: |
| | PLEASE COMPETE ALL CIRCUITING ON PLANS AND CORRELATE |
| | WITH THE SUBMITTED PANEL SCHEDULES. PLEASE BE SURE TO |
| | SEE PREVIOUS PLANS FOR SHELL BUILDING AND CIRCUITING |
| | PER 700.12F FOR ALL EMERGENCY AND EXIT LIGHTS. |
| | 106.1.2, |
| | 408.4 NEC.THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM |
| | THE NEC. PLEASE BE SURE ALL AREAS, ROOMS DESIGNATIONS |
| | ETC COORDINATE WITH THE CIRCUITS ON PANEL SCHEDULES |
| | SPECIFIC. |
| | |
| | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO |
| | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | ** PLEASE SEE THE SECTION OF THE COMMENTARY WAS ADDED |
| | TO POWER AND LIGHTING SHEETS WHICH IS NOT WHAT COMMENT |
| | WAS REQUESTING. PLEASE SEE THIS COMMENT WAS STATING THE |
| | CIRCUITS WHICH ARE ALREADY SHOWN ON THE SUBMITTED PANEL |
| | SCHEDULE WERE TO BE MORE SPECIFIC AND NOT TO ONLY STATE |
| | *OUTLET* OR *LIGHTING*. MAY USE ALPHA OR NUMERIC |
| | DESIGNATIONS OF CIRCUITS. |
| | PLEASE SEE THE PLANS WHICH HAD THIS NOT STATE ON PLANS |
| | ALSO IS QUOTING THE INCORRECT CODE SECTION. |
| | THIS APPEARS TO HAVE BEEN A MISPRINT. |
| | |
| | 12) NOTE:PLEASE SEE 517 OF THE NEC AND EXPAND ON ANY |
| | LOCATIONS PER 517 AND 517.13(A) AND (B) |
| | PLEASE EXPAND ON THE GROUNDING REQUIRED. |
| | THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE |
| | CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE |
| | FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO |
| | HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES |
| | THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO |
| | IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL |
| | INVOLVED. |
| | **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS |
| | IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE |
| | NOT. |
| | |
| | 13) NOTE: PLEASE COORDINATE PLANS WITH THE ELECTRICAL |
| | RISER DIAGRAM. |
| | PLEASE SEE THE MAIN ELECTRICAL ROOM LAYOUT DOES NOT |
| | CONTAIN ALL THE EQUIPMENT AS SHOWN ON RISER. PLEASE |
| | ALSO PROVIDE THE SIZES FOR THE GUTTER AS SHOWN. PLEASE |
| | SEE 110.26, 366. |
| | PLEASE SEE THE FOLLOWING EXTRACTED FROM THE NEC FOR USE |
| | OF READING AS THE GUTTER SHALL NOT EXTEND INTO THE |
| | WORKING CLEARANCE AREA BY MORE THAN 6 INCHES. |
| | |
| | *110.26(A)(3) |
| | (3) HEIGHT OF WORKING SPACE THE WORK SPACE SHALL BE |
| | CLEAR AND EXTEND FROM THE GRADE, FLOOR, OR PLATFORM TO |
| | THE HEIGHT REQUIRED BY 110.26(E). WITHIN THE HEIGHT |
| | REQUIREMENTS OF THIS SECTION, OTHER EQUIPMENT THAT IS |
| | ASSOCIATED WITH THE ELECTRICAL INSTALLATION AND IS |
| | LOCATED ABOVE OR BELOW THE ELECTRICAL EQUIPMENT SHALL |
| | BE PERMITTED TO EXTEND NOT MORE THAN 150 MM (6 IN.) |
| | BEYOND THE FRONT OF THE ELECTRICAL EQUIPMENT. |
| | ** COMMENTARY** |
| | IN ADDITION TO REQUIRING A WORKING SPACE TO BE CLEAR |
| | FROM THE FLOOR TO A HEIGHT OF 61/2 FT OR TO THE HEIGHT |
| | OF THE EQUIPMENT, WHICHEVER IS GREATER, 110.26(A)(3) |
| | PERMITS ELECTRICAL EQUIPMENT LOCATED ABOVE OR BELOW |
| | OTHER ELECTRICAL EQUIPMENT TO EXTEND INTO THE WORKING |
| | SPACE NOT MORE THAN 6 IN. THIS REQUIREMENT ALLOWS THE |
| | PLACEMENT OF A 12 IN. ? 12 IN. WIRE-WAY ON THE WALL |
| | DIRECTLY ABOVE OR BELOW A 6 IN. DEEP PANEL-BOARD |
| | WITHOUT IMPINGING ON THE WORKING SPACE OR COMPROMISING |
| | PRACTICAL WORKING CLEARANCES. THE REQUIREMENT CONTINUES |
| | TO PROHIBIT LARGE DIFFERENCES IN DEPTH OF EQUIPMENT |
| | BELOW OR ABOVE OTHER EQUIPMENT THAT SPECIFICALLY |
| | REQUIRES WORKING SPACE.** |
| | |
| | PLEASE SIZE GUTTERS ACCORDINGLY WHICH ARE BEING SHOWN |
| | DIRECTLY IN FRONT OF MAINS, EQUIPMENT AND METERS WHICH |
| | COULD BE A SAFETY HAZARD. |
| | |
| | 14) NOTE: PLEASE BE SURE TO GO OVER LOAD CALCULATIONS. |
| | PLEASE BE SURE TO SEE THE PREVIOUS REVIEW COMMENTS FOR |
| | ALL LOADS TO BE SHOWN. |
| | PLEASE SEE THE 2005 NEC FOR REQUIRED METHODS. 220.12, |
| | 220.14, 220.42, 220.44 AND ALL PREVIOUS SECTIONS AS |
| | PREVIOUSLY NOTED. |
| | PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR SERVICE |
| | AND EACH OF THE PANELS AS BEING SHOWN EVEN THOSE BEING |
| | SET ASIDE FOR FUTURE USE. |
| | PLEASE SEE THE ENERGY CALCULATIONS INDICATE TWO |
| | ELECTRIC WATER HEATERS YET THE CALCULATIONS DO NOT |
| | INCLUDE THESE, PANEL SCHEDULES? PLEASE SEE 422.13 AS |
| | THESE ARE REQUIRED TO BE SHOWN AT 125%. |
| | PLEASE SEE ALL OF 220. |
| | PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| | LOADS AND LARGEST MOTORS LOADS AT 125%. |
| | FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| | |
| | 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | ONE COPY OF PLANS MAY BE RETAINED BY THIS OFFICE. |
| | |
| | AS STATED ON PREVIOUS REVIEW: |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |