| 2007-08-31 12:14:41 | 5205 GREENWOOD AVE |
| | BUILD-OUT3RD REVIEW |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07040621 |
| | ADD: 5205 GREENWOOD |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)689-8880 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | 3RDREVIEW |
| | ACTION: DENIED |
| | |
| | NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED |
| | PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN |
| | ADDITION TO THIS STRUCTURE. |
| | PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE |
| | 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS |
| | : LEVEL 3 AND CHAP 9 FOR ADDITIONS |
| | AS WELL AS 2006 FBC BUILDING.. |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS NULL & VOID. |
| | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION |
| | SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5) SEMI-COMPLIED.SHEET GV-101 DOOR 174A IS MISSING |
| | THE 18? ON THE PULL SIDE OF DOOR AT LATCH SIDE OF DOOR. |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE |
| | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | 6-7A) COMPLIED. |
| | |
| | 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS |
| | OR FIRE SPRINKLERS ARE ACTIVATED? |
| | |
| | 7C)2ND REQUEST. SEMI-COMPLIED, THE DETAIL# 03 ON |
| | AF-402 IS TO BE 1HR RATED WALL PLEASE PROVIDE THE UL |
| | NUMBER OR US GYPSUM NUMBER THAT ALLOWS DRYWALL ON ONLY |
| | ONE SIDE OF THE ASSEMBLY? PLEASE PROVIDE THE COMPLETE |
| | UL LISTING NUMBER, PROVIDE A DETAIL OF THE UL LISTING |
| | AND PROVIDE A SECTION OF THE L HOUR RATED WALL.706.3 |
| | FIRE RESISTANCE RATINGS. |
| | |
| | 7D-9) COMPLIED. |
| | |
| | 10) 2ND REQUEST,GV-102 ELEVATOR LOBBY 200 INDICATES A |
| | PAIR OF DOORS AND THE OPPOSITE END OF THIS AREA THERE |
| | APPEARS TO BE GLASS, IT IS NOT CLEAR IF THIS IS A WALL |
| | OR IF IT IS A GLASS HANDRAIL, PLEASE PROVIDE A CUT |
| | THROUGH THIS SECTION. SEE ATRIUM REQUIREMENTS 404.5 SEE |
| | EXCEPTION (1).THE PLAN ACTUALLY INDICATES THE 1 HR |
| | RATED WALL TO FALL IN LINE WITH DOOR LINE. SHEET AF-601 |
| | INDICATES DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE |
| | PROVIDE THIS INFORMATION FOR THESE DOORS AND THE RATED |
| | DOORS FOR THE FIRST FLOOR. |
| | SHEET EA101 & EA 102 INDICATE SYMBOLS THAT |
| | POSSIBLY TIE TO THE ALARM PANEL BUT SHEET |
| | EC-001 WHICH IS THE FIRE ALARM SYMBOLS AND NOTES IS |
| | MISSING PLEASE PROVIDE. ADDITIONAL INFORMATION REQUIRED |
| | 106.1.2*. |
| | |
| | 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN |
| | ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE |
| | STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS, |
| | HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL, |
| | AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT |
| | THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN |
| | THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN |
| | ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION |
| | 505 . |
| | |
| | 11A-11B) COMPLIED. SMOKE CONTROL NOT REQUIRED SECTION |
| | 404 EXCEPTIONS. |
| | |
| | 12-17) COMPLIED. |
| | |
| | 18)SEMI-COMPLIED, THE FRONTS AND INTERIOR OF THE |
| | CABINETS ARE TO BE REMOVED FOR FRONTAL APPROACH |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 19-20) COMPLIED. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |