| 2007-06-27 12:56:21 | *****DENIED***** |
| | |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.AS PERTAINS TO THE PROJECT CODE DATA ON GV-101, |
| | REFERENCE THE FOLLOWING:NFPA 1 (2003 EDITION),NFPA |
| | 101 (2003 EDITION),ANDFLORIDA FIRE PREVENTION CODE |
| | (2004 EDITION). |
| | |
| | 03.ON SHEET GV-101, EXPLAIN THE DIFFERENCE BETWEEN FE |
| | AND FHV LEGEND SYMBOLS.BOTH INDICATE FIRE |
| | EXTINGUISHER. |
| | |
| | 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | GREENWOOD AVENUE, SHOW/DISPLAY THE NUMERICAL ADDRESS ON |
| | THE BUILDING.PLEASE BE REMINDED EVEN A MARKEE OR |
| | MONUMENT SIGN IS USED AT GREENWOOD AVENUE, THE |
| | NUMERICAL ADDRESS SHALL BE ON THE STRUCTURE AS PER WEST |
| | PALM BEACH ADDRESSING CODE. |
| | |
| | 05.PLANS INDICATE THAT THIS BUILDING WILL BE FIRE |
| | SPRINKLERED IN CONJUNCTION WITH A FIRE ALARM SYSTEM. |
| | SHOW THE LOCATION OF THE REQUIRED PREMISES ACCESS/KNOX |
| | BOX AT THE APPROPIATE EXTERIOR ELEVATION.FOR |
| | APPLICATIONS, CONTACT THE WPB FIRE PREVENTION AT |
| | 561-804-4724. |
| | |
| | 06.ON SHEET GV-102,EXPLAIN THE USE OF THE SLEEP |
| | ROOM (226). |
| | |
| | 07.ON SHEET GV-102, EXPLAIN THE AREA LOCATED IN THE |
| | TOP RIGTH CORNER IN THE CONFERENCE PRESENTATION ROOM |
| | (210).HOW IS ACESS GAINED? |
| | |
| | 08.PLEASE CLARIFY/INDICATE SYMBOL FOR THE EMERGENCY |
| | LIGTS ON SHEETS AR-101, AR-102, EL-101, AND EL102. |
| | |
| | 09.INTERIOR FLOOR FINISH SHALL COMPLY WITH SECTION |
| | 10.2 OF NFPA 101;INTERIOR FLOOR FINISH IN EXIT |
| | ENCLOSURES SHALL BE CLASS I OR CLASS II.BE SPECIFIC |
| | |
| | 10.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL |
| | BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS |
| | CORRIDORS;SHALL BE CLASS A, CLASS B, OR CLASS C IN |
| | ALL OTHER AREAS. |
| | |
| | 11.ON SHEET FS-101, INDICATE FROM WHOM THE FIRE FLOW |
| | DATA WAS OBTAINED. |
| | |
| | 12.SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | FIRE SPRINKLER REMODEL AND FIRE ALARM SYSTEMS SCOPE OF |
| | WORK. |
| | |
| | 13.FIRE ALARM SYSTEM TO BE CLASS A OR FULLY |
| | ADDRESSABLE. |
| | |
| | 14.FIRE ALARM SYSTEM SHALL BE UL CERTIFIED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 15.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. |
| | |
| | 16.DOORS AS A MEANS OF EGRESS COMPONENT SHALL COMPLY |
| | WITH SECTION 7.2.1 OF NFPA 101. |
| | |
| | 17.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK |
| | ONLY IF THE LOCK OR LATCH IS PANIC HARDWARE OR FIRE |
| | EXIT HARDWARE. |
| | |
| | 18.ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF |
| | ASME A17.1 (NEW ELEVATORS) OR ASME A17.3 (EXISTING |
| | ELEVATORS). |
| | |
| | 19.WARNING SIGNS (DO NOT USE IN THE EVENT OF A FIRE) |
| | ARE REQUIRED IN THE ELEVATOR LOBBIES. |
| | |
| | 20.ALL FIRE DOORS AND WINDOWS TO COMPLY WITH NFPA 80, |
| | FIRE DOORS AND WINDOWS. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE THE ITEMS WERE ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |