| 2007-05-30 16:57:08 | BUILDING PLAN REVIEW |
| | PERMIT: 07040621 |
| | ADD: 5205 GREENWOOD |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)689-8880 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | NOTE! THIS PROJECT HAS BEEN SUBMITTED AS A PHASED |
| | PROJECT, THERE HAS BEEN A REMODEL ELEMENT, AND AN |
| | ADDITION TO THIS STRUCTURE. |
| | PLEASE NOTE THAT THESE PLANS WILL BE REVIEWED UNDER THE |
| | 2004 EXISTING BUILDING CODE 2006 EDITION , ALTERATIONS |
| | : LEVEL 3 AND CHAP 9 FOR ADDITIONS |
| | AS WELL AS 2006 FBC BUILDING.. |
| | |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS NULL & VOID. |
| | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION |
| | SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3A) SHEET GV-101 TYPE OF CONSTRUCTION: IV HEAVY TIMBER |
| | PLEASE LOOK AT |
| | SECTION 602 FOR BUILDING CONSTRUCTION CLASSIFICATIONS |
| | AND TABLE 503.THIS BUILDING IS NOT |
| | A HEAVY TIMBER DESIGN. NOTE IF IT IS AN "A OR B" |
| | CLASSIFICATION. |
| | |
| | 3B) GV-101 INDICATES 9006 SQ FT FIRST FLOOR WHILE THE |
| | 2ND FLOOR HAS 9170, THE FOOTPRINT ON THE FIRST FLOOR IS |
| | LARGER HAVING MORE ARERA, PLEASE RECALCULATE PLUS |
| | COVERED WALKWAY! |
| | |
| | 3C) NOTE INCREASES THAT CAN BE TAKEN FOR A FULLY |
| | SPRINKLERED BUILDING(AREA INCREASES)! |
| | |
| | 4) PLANS ALSO INDICATE THE BUILDING DESIGN IS THE 2004 |
| | FBC, PLANS SUBMITTED |
| | AFTER DEC 12,2006 FALL IN UNDER THE 2006 FBC. |
| | |
| | 5)SHEET GV-101 INDICATES DOORWAYS IN THE CORRIDOR |
| | THAT DO NOT HAVE IDENTIFYING TAGS, THE FIRST DOOR ISUE |
| | |
| | IS LOCATED BETWEEN ROOM 167 AND ROOM 171, THE SECOND |
| | DOOR IS LOCATED BETWEEN |
| | ROOMS 193 AND 125B. IN BOTH CASES IT APPEARS THERE IS |
| | NOT 18" ON THE LATCH SIDE OF THE DOORWAY. 11-4.13.6 |
| | MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| | CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL |
| | BE AS SHOWN IN FIG. 25. THE FLOOR OR |
| | GROUND AREA WITH IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 6)PLANS INDICATE THIS IS A BUSINESS OCCUPANCY, THE |
| | PLANS DO NOT IDENTIFY IF IT IS A SINGLE TENANT? THE |
| | FIRST FLOOR DOES HAVE TWO |
| | WAITING ROOMS 110 AND 150? 106.1.2* ADD INFO REQUIRED |
| | AND708.1(5). |
| | |
| | 7) GV-102 THE PLANS INDICATE ON THE MAIN ENTRY STAIR |
| | WITH ACOILING FIRE RATED DOOR AT THE HEAD OF THE |
| | SECOND STORY LANDING AND WHAT APPEARS TO BE A 1 HOUR |
| | RATED WALL. |
| | SHEET AF-402 DETAIL 03 INDICATES A HORIZONTAL COILING |
| | FIRE DOOR. |
| | 7A) PLEASE SUBMIT PRODUCT INFORMATION FOR A 1 HR RATED |
| | ASSEMBLY. |
| | 7B) PROVIDE HOW THIS DOOR WILL CLOSE IF THE FIRE ALARMS |
| | OR FIRE SPRINKLERS ARE ACTIVATED? |
| | 7C) THE DETAIL# 03 ON AF-402 IS TO BE 1HR RATED WALL |
| | PLEASE PROVIDE THE UL NUMBER OR US GYPSUM NUMBER THAT |
| | ALLOWS DRYWALL ON ONLY ONE SIDE OF THE ASSEMBLY? 7D) |
| | PLEASE INDICATE HOW ONE WOULD GAIN ACCESS TO DO |
| | MAINTENCE WORK ON THE COILED FIRE DOOR ? ADDITIONAL |
| | COMMENTS MAY APPEAR ON THESE ITEMS ONCE THE RESPONCES |
| | ARE REVIEWED. |
| | |
| | 8)GV-102 PLANS APPEAR TO HAVE A SLEEP STUDY AREA WITH |
| | A CONTROL ROOM. PLEASE PROVIDE ADDITIONAL INFORMATION |
| | AS TOTHE FUCTION OF THIS AREA? WILL THE PATIENTS BE |
| | THERE OVER 24 HRS? |
| | WILL THE PATIENTS BE MEDICATED? AND WILL THERE BE MORE |
| | THAN ONE PATEINT THERE SLEEPING? |
| | |
| | 9)GV-102 ROOM 210 CONFERENCE PRESENTATION THERE |
| | APPEARS TO BE A SEPERATE ROOM IN THE UPPER RIGHT CORNER |
| | WITH NO IDENTIFICATION? PLEASE PROVIDE ADDITIONAL |
| | INFORMATION. 106.1.2* |
| | |
| | 10) GV-102 ELEVATOR LOBBY 200 INDICATES A PAIR OF DOORS |
| | AND THE OPPOSITE END OF THIS AREA THERE APPEARS TO BE |
| | GLASS, IT IS NOT CLEAR IF THIS IS A WALL OR IF IT IS A |
| | GLASS HANDRAIL, PLEASE PROVIDE A CUT THROUGH THIS |
| | SECTION. SEE ATRUIM REQUIREMENTS 404.5 SEE EXCEPTION |
| | (1).THE PLAN ACTUALLY INDICATES THE 1 HR RATED WALL |
| | TO FALL IN LINE WITH DOOR LINE. SHEET AF-601 INDICATES |
| | DOORS AND FRAMES BUT NO DOOR SCHEDULE. PLEASE PROVIDE |
| | THIS INFORMATION FOR THESE DOORS AND THE RATED DOORS |
| | FOR THE FIRST FLOOR. |
| | |
| | 11) NOTE, BY DEFINITION, THIS AREA (LOBBY 100) IS AN |
| | ATRIUM. ATRIUM . AN OPENING CONNECTING TWO OR MORE |
| | STORIES OTHER THAN ENCLOSED STAIRWAYS, ELEVATORS, |
| | HOISTWAY, ESCALATORS, PLUMBING, ELECTRICAL, |
| | AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH IS CLOSED AT |
| | THE TOP AND NOT DEFINED AS A MALL. STORIES, AS USED IN |
| | THIS DEFINITION, DO NOT INCLUDE BALCONIES WITHIN |
| | ASSEMBLY GROUPS OR MEZZANINES THAT COMPLY WITH SECTION |
| | 505 . |
| | |
| | 11A)404.4 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL |
| | BE INSTALLED IN ACCORDANCE WITH SECTION 909 . |
| | 11B)404.6 STANDBY POWER. EQUIPMENT REQUIRED TO |
| | PROVIDE SMOKE CONTROL SHALL BE CONNECTED TO A STANDBY |
| | POWER SYSTEM IN ACCORDANCE WITH SECTION 909.11 . |
| | |
| | 12) GV-102ROOM 223 PLEASE SHOW THE CLEAR FLOOR SPACE |
| | REQUIRED FOR PLUMBING FIXTURES, IT APPEARS THAT THE |
| | DOORWAY MAY SWING INTO THE LAV CLEAR FLOOR SPACE. |
| | 11-4.19.3 CLEAR FLOOR SPACE . |
| | A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY |
| | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE |
| | PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD |
| | APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR |
| | OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM |
| | OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE |
| | FIGURE 32 ). |
| | |
| | 13) GV-102 ROOM XXX SHELL IS THIS THE SAME TENANT |
| | SPACE? |
| | |
| | 14)PLEASE DEVELOP A DOOR IDENIFICATION SYSTEM NO |
| | DOORS ARE IDENTIFIED ON EITHER FLOOR. |
| | |
| | 15) GV-102 CONFERENCE ROOM 210 HAS AN OCCUPANT LOAD OF |
| | APPROX 114 PEOPLE PLEASE SEE TABLE 1016.1 FOR ASSEMBLY |
| | OCCUPANCIES, OCCUPANT LOADS SERVED BY CORRIDORS, TABLE |
| | 1016.1WITH SPRINKLERS SYSTEMS AND OCCUPANT LOADS >30 |
| | REQUIRING 1 HR RATED CORRIDORS. |
| | |
| | 16) GV-102 ROOM 211 ELEVATOR MACHINE ROOM. 3006.4 |
| | MACHINE ROOMS AND MACHINERY SPACES. |
| | ELEVATOR MACHINE ROOMS AND MACHINERY SPACES SHALL BE |
| | ENCLOSED WITH CONSTRUCTION HAVING A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THE REQUIRED RATING OF THE |
| | HOISTWAY ENCLOSURE SERVED BY THE MACHINERY. OPENINGS |
| | SHALL BE PROTECTED WITH ASSEMBLIES HAVING A |
| | FIRE-RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR |
| | THE HOISTWAY ENCLOSURE DOORS. |
| | |
| | 17) GV-102 ROOM 211 3006.1 ACCESS.AN APPROVED MEANS |
| | OF ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE ROOMS . |
| | AN APPROVED ACCESS DOES NOT HAVE MEANS OF EGRESS |
| | THROUGH TENANT SPACES. |
| | |
| | 18)AF-210 LOUNGE SINK IS CABINET ELEVATION INDICATES |
| | A 3'-0" ELEVATION. SINKS:11-4.24.2 SINKS, HEIGHT. |
| | SINKS SHALL BE MOUNTED WITH THE COUNTER NO HIGHER THAN |
| | 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| | SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | AT LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 19) AF-320 VARIOUS WALLS INDICATE THAT SOME MAY REQUIRE |
| | FIRE RATINGS, PLEASE PROVIDEINFORMATION ON THE FLOOR |
| | TO FLOOR ORFLOOR TO ROOF/ CEILING ASSEMBLIES. 713.1 |
| | GENERAL. JOINTS INSTALLED IN OR BETWEEN |
| | FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING |
| | ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| | BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME |
| | PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE |
| | RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH |
| | IT IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS SHALL BE |
| | TESTED IN ACCORDANCE WITH SECTION 713.3 . THE VOID |
| | CREATED AT THE INTERSECTION OF A FLOOR/CEILING ASSEMBLY |
| | AND AN EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 713.4 . |
| | |
| | 20) AF-401 GRAND STAIR SECTION AT THE TOP OF THE |
| | STAIRCASE THE HORIZONTAL PROJECTION OFTHE HANDRAIL IS |
| | TO BE A MINIMUM OF 1'-0" LONG. 11-4.9.4 |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |