| Plan Review Notes For Permit 07040606 |
| Permit Number |
07040606 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-12 10:52:29 | | | | | | | DENIED | | | | | | 1)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE | | | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES, | | | AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/ | | | FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN | | | ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS | | | PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG. | | | ****PLEASE NOTE THAT THE NOA SUBMITTED DOES NOT INCLUDE | | | THE DOORS THEY ARE UNDER SEPARATE NOA.**** | | | | | | 2)PROVIDE 2 COPIES OF LAYOUT AND INCLUDE THE WIDTH OF | | | EACH UNIT BETWEEN MULLIONS IN ORDER TO ESTABLISH DESIGN | | | PRESSURE. | | | | | | 3)DESIGN PRESSURE IN THE 2004 FBC HAVE BEEN UPDATED | | | WITH THE 2006 AMENDMENTS, ANY BUILDING IN A NORMALLY | | | EXPOSURE BCATEGORY THAT HAS OPEN TERRAIN (INCLUDES | | | BODIES OF WATER) IN ANY QUADRANT FOR A DISTANCE OF 600 | | | FT WILL BE CONSIDERED EXPOSURE C. | | | | | | 4)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT IS | | | REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|