| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, , |
| | 2004 FBC AS AMENDED, CHAPTER 1. |
| | AND FOUND NONE COMPLIANT WITH THE FOLLOWING: ALL |
| | COMMENTS ARE REGARDING SHEET 2 OF 4. |
| | |
| | 1} THE ELECTRICAL RISER DIAGRAM DOES NOT INCLUDE A |
| | DISCONNECTING MEANS REQUIRED PER 230.70(A)(1) NEC "THE |
| | SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A |
| | READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A |
| | BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF |
| | ENTRANCE OF THE SERVICE CONDUCTORS." THE SITE/FLOOR |
| | PLAN INCLUDES A DISCONNECT AT THE METER LOCATION. |
| | CORRELATE THE SERVICE EQUIPMENT . |
| | |
| | 2} THE RISER STATES A 200 AMP SERVICE, THE PANEL IS |
| | LABLED 150 AMPS, AND THE GROUNDING ELECTRODE CONDUCTOR |
| | , #6 CU, IS SIZED FOR A150 AMP SERVICE PER 250.66 NEC. |
| | CORRELATE THE EQUIPMENT. |
| | |
| | 3}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE, FOR ALL FEEDERS FROM THE WEATHERHEAD TO |
| | THE PANEL. 215.5 NEC |
| | |
| | 4} CIRCUIT # 27 ON THE PANEL SCHEDULE LABLED "DINING |
| | ROOM REC" IS A 15 AMP CIRCUIT. PER 210.52(B)(1) THIS |
| | CIRCUIT MUST BE 20 AMP (#12 WIRE). |
| | |
| | 5} THE RECEPTACLE LOCATION ON THE PENINSULAR MAY NOT |
| | MEET THE REQUIRWMENTS OF 210.52(C)(5) EXCEPTION, IF THE |
| | COUNTER EXTENDS MORE THAN 6", THE RECEPTACLE MAY NEED |
| | TO BE RELOCATED TO THE END AND PLACED WITHIN12" FROM |
| | THE TOP. SEE ARTICLE AND EXCEPTION. |
| | |
| | 6} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. |
| | SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND |
| | 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. ANSWER |
| | REVIEW COMMENTS IN WRITING. |
| | |