| Plan Review Notes For Permit 07040598 |
| Permit Number |
07040598 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-18 09:04:29 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 2} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE | | | AND AMPERE RATING, MAIN LUG OR MAIN BREAKER. | | | | | | 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW | | | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE | | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | | DISTINGUISHED FROM ALL OTHERS." | | | | | | 4} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | | FOR CLARITY IN THE FIELD. | | | | | | 5} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | | PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. | | | | | | 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C). AND 210.8(A)(6) GFI. CHECK PLAN | | | FOR SPACING REQUIREMENTS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|