2007-05-12 10:02:37 
  
 DENIED
  
 1)DESIGN PRESSURE IN THE 2004 FBC HAVE BEEN UPDATED
 WITH THE 2006 AMENDMENTS, ANY BUILDING IN A NORMALLY
 EXPOSURE BCATEGORY THAT HAS OPEN TERRAIN (INCLUDES
 BODIES OF WATER) IN ANY QUADRANT FOR A DISTANCE OF 600
 FT WILL BE CONSIDERED EXPOSURE C. PLEASE UPDATE
 SCHEDULE TO REFLECT THIS EXPOSURE.
  
 2)ENGINEERED WIND LOADS THAT ARE NOT PART OF THE
 PRODUCT APPROVAL SHALL BE SIGNED AND SEALED BY THE
 ENGINEER. THE SHEET SUBMITTED IS FOR DRAWING 02-547 NOT
 05-578 . YOU MAY USE SUCH TABLES OR CODE BOOK TO FIND
 DESIGN PRESSURES BUT DO NOT SUBMIT OR THEY ARE REQUIRED
 TO BE SIGNED AND SEALED.
  
 3)SCHEDULE DOES NOT MATCH DRAWINGS PLEASE NOTE THAT
 THE C3 CONNECTION CIRCLED IN DRAWING IS FOR THE TOP
 CONNECTION AND SCHEDULE IS USING IT ON THE BOTTOM.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716