| Plan Review Notes For Permit 07040597 |
| Permit Number |
07040597 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-12 10:02:37 | | | | | | | DENIED | | | | | | 1)DESIGN PRESSURE IN THE 2004 FBC HAVE BEEN UPDATED | | | WITH THE 2006 AMENDMENTS, ANY BUILDING IN A NORMALLY | | | EXPOSURE BCATEGORY THAT HAS OPEN TERRAIN (INCLUDES | | | BODIES OF WATER) IN ANY QUADRANT FOR A DISTANCE OF 600 | | | FT WILL BE CONSIDERED EXPOSURE C. PLEASE UPDATE | | | SCHEDULE TO REFLECT THIS EXPOSURE. | | | | | | 2)ENGINEERED WIND LOADS THAT ARE NOT PART OF THE | | | PRODUCT APPROVAL SHALL BE SIGNED AND SEALED BY THE | | | ENGINEER. THE SHEET SUBMITTED IS FOR DRAWING 02-547 NOT | | | 05-578 . YOU MAY USE SUCH TABLES OR CODE BOOK TO FIND | | | DESIGN PRESSURES BUT DO NOT SUBMIT OR THEY ARE REQUIRED | | | TO BE SIGNED AND SEALED. | | | | | | 3)SCHEDULE DOES NOT MATCH DRAWINGS PLEASE NOTE THAT | | | THE C3 CONNECTION CIRCLED IN DRAWING IS FOR THE TOP | | | CONNECTION AND SCHEDULE IS USING IT ON THE BOTTOM. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|