Notes
Date Text
2007-04-27 08:04:24 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} INDICATE DISCONNECTING MEANS PER 225.31, LOCATION
 225.32 AND GROUNDING PER 250.32.
  
 2} SHEET 4 SHOWS A RISER DIAGRAM. INDICATE IF PART OF
 THIS APPLICATION IS FOR NEW SERVICE EQUUIPMENT.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 5} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 AFTER SUBMITTING THE ABOVE FOR REVIEW THERE MAY BE
 OTHER COMMENTS.
  