| Plan Review Notes For Permit 07040578 |
| Permit Number |
07040578 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-27 08:04:24 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} INDICATE DISCONNECTING MEANS PER 225.31, LOCATION | | | 225.32 AND GROUNDING PER 250.32. | | | | | | 2} SHEET 4 SHOWS A RISER DIAGRAM. INDICATE IF PART OF | | | THIS APPLICATION IS FOR NEW SERVICE EQUUIPMENT. | | | | | | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW | | | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE | | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | | DISTINGUISHED FROM ALL OTHERS." | | | | | | 5} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | AFTER SUBMITTING THE ABOVE FOR REVIEW THERE MAY BE | | | OTHER COMMENTS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|