| Date |
Text |
| 2008-03-03 09:52:13 | ** DENIED 3RD REVIEW ** |
| | |
| | ** MANY COMMENTS ARE NEW AS THESE THINGS ARE JUST NOW |
| | BEING SHOWN. |
| | |
| | 1) NOTE: PLEASE SEE 424.3B AS THE MINIMUM OVER CURRENT |
| | PROTECTION FOR THE AHU NEEDS TO BE AT 125%. SHOWS 30AMP |
| | ON 10KW HEAT WHICH IS NOT PERMITTED. |
| | PLEASE ALSO COORDINATE THE AHU HEAT ON CALCULATIONS |
| | WITH THE MECHANICAL PLANS AS MECHANICAL SHOWS 10KW AND |
| | ELECTRICAL CALCULATIONS SHOWS 8KW AND 9KW. |
| | |
| | 2) NOTE: PLEASE INCLUDE DETAILS FOR GROUNDING ELECTRODE |
| | SYSTEM.PLEASE SEE 250.50, 250.56, 250.52(5) PLEASE |
| | INCLUDE 2-GRND RODS, AND COLD WATER PIPE (METAL). |
| | MAY NOT QUOTE 250 AS GENERAL IN LIEU OF DETAILS. |
| | |
| | 3) NOTE: PLEASE INCLUDE THE ACTUAL AIC RATING OF MAIN. |
| | PLANS INCLUDE A LETTER FROM FPL WHICH GIVES AVAILABLE |
| | FAULT CURRENT HOWEVER THIS DOES NOT GIVE THE RATING OF |
| | WHAT THE MAINS/EQUIPMENT WILL BE. THE SELECTION OF THE |
| | AIC OF EQUIPMENT IS DETERMINED FROM THE AVAILABLE FAULT |
| | CURRENT HOWEVER THE SELECTION IS NOT DONE BY FPL. |
| | 110.9 |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | DINING ROOM LOADS. THE PANEL SCHEDULE SHOWS TWO |
| | DEDICATE CIRCUITS WHICH REQUIRES THE LOAD TO BE FIGURED |
| | FOR DINING ROOM RECEPTACLE CIRCUITS ARE TO BE FIGURED |
| | IN ADDITION TO THE TWO SMALL APPLIANCE CIRCUITS. |
| | 210.52B1, 210.11C1, 220.53 |
| | |
| | 5) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS WITH |
| | RESPECT TO RETURN AIR. |
| | ELECTRICAL PLANS SHOWS AHU BEING OPEN TO CLOSET YET THE |
| | OTHER TWO SHEETS SHOWS THE AHU AS CLOSED IN. |
| | PLEASE KNOW THAT THE AHU MAY NOT CONTAIN OVER CURRENT |
| | PROTECTION IN A CLOSET IN CLOSE PROXIMITY TO EASILY |
| | IGNITABLE MATERIALS. |
| | 240.24, 110.26 |
| | |
| | 6) NOTE: PLEASE SEE THE LOAD FOR THE DISPOSAL IS NOT |
| | FIGURED INTO THE LOAD CALCULATIONS. THIS CIRCUIT IS |
| | SHOWN ON PANEL SCHEDULE. |
| | 220 |
| | PLEASE ALSO SEE THE KITCHEN ELECTRICAL PLANS DO NOT |
| | INCLUDE THE RECEPTACLE FOR THIS DISPOSAL. WILL IT BE |
| | SWITCHED? OR SELF STARTING? |
| | |
| | 7) NOTE: PLEASE COORDINATE THE SUB PANELS AS THE RISER |
| | SHOWS THESE A MLO WHICH IS CORRECT AND THE PANEL |
| | SCHEDULES SHOW THESE AS MDO? |
| | SEEMS TO BE A MISPRINT. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |