| 2007-11-16 15:27:00 | RESIDENTIAL REPAIRS BUILDING REVIEW SECOND CHECKLIST. |
| | REVIEW DONE UNDER EXISTING BUILDING CODE 2004, FLORIDA |
| | RESIDENTIAL CODE 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PLANS SUBMITTED DON'T SHOW ANY WORK TO BE PERFORMED |
| | OTHER THAN ELECTRICAL, PLUMBING AND MECHANICAL.PLANS |
| | NEED TO SPECIFY EXTENT OF WORK AND SPECIFIC LOCATION OF |
| | WORK TO BE PERFORMED AS CALLED FOR IN THE PERMIT |
| | APPLICATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 2- NOWIS NOT CLEAR WHAT'S THE REAL SCOPE OF WORK TO |
| | BE PERFORMED. PERMIT APPLICATION CALLS FOR "R/R |
| | DRYWALL, INSULATION, ELECTRIC, R/R |
| | TUB/TOILET/SINK/VANITY".OWNER RESPONSE LETTER STATES |
| | THATNO WINDOWS ARE TO BE REPLACED (COMMENT FROM |
| | PREVIOUS CHECKLIST),ONLY THE WINDOW A/C UNITS ARE TO |
| | BE REPLACED. NOW IT'S NOT CLEAR WHY REPLACING THE |
| | WINDOW UNITS AND ALSOSHOWING A/C PLANS?. IN ADDITION, |
| | OWNER STATES THAT THERE ARE SOME WALLS THAT NEED THE |
| | WOODSTUDS TO BE REPLACED.PLANS DON'T SHOW ANY OF |
| | THIS WORK OR ANY SPECIFIC LOCATION FOR THIS WORK TO BE |
| | PERFORMED. |
| | PLEASE,COORDINATE ALL WORK TO BE PERFORMED IN THIS |
| | HOUSE AND PROVIDE SUCH INFORMATION IN THE PLANS DRAWN |
| | BY THE CERTIFIED BUILDING CONTRACTOR(SANTORO |
| | CONSTRUCTION, INC.) WHO DREW THE PLANS. |
| | |
| | 3- UPDATE VALUATION TO INCLUDE ALL WORK TO BE PERFORMED |
| | IN ALL TRADES AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS |
| | TO FBC 2004.REVISED VALUE OF $11,000 DOESN'T COVER |
| | ALL PROPOSED SCOPE OF WORK. |
| | |
| | 4- PLANS NEED TO HAVE THE NAME AND ORIGINAL SIGNATURE |
| | OF THE CERTIFIED BUILDING CONTRACTOR WHO DESIGNED THE |
| | THE PLANS AS REQUIRED BY SEC. 106.3.4.3CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 5- NEED RECORDED NOTICE OF COMMENCEMENT. ONE PROVIDED |
| | WAS RECORDED ON 04/19/2007. NOTICE OF COMMENCEMENT IS |
| | EXPIRED AFTER 90 DAYSIF WORK IS NOT STARTED AFTER IT |
| | WAS RECORDED. NEED TO PROVIDE RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |