Plan Review Notes
Plan Review Notes For Permit 07040545
Permit Number 07040545
Review Stop M
Sequence Number 2
Notes
Date Text
2007-11-13 08:27:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MAIN TRUNK LINE (DUCT) STILL NEEDS TO BE SIZED,
 (SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN), SEE WPB
 AMEND. 106.3.5.4 (10).
  
 2) THE RETURN AIR TRANSFER DUCT STILL NEEDS TO BE
 SIZED, (SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN), SEE
 FBC/R M1602.4.
  
 3) SHOW THE MANUFACTURER'S NAME OF THE A/C SYSTEM ON
 THE PLAN.
  
 4) SHOW THE HEATER KW ON THE PLAN IF ONE IS TO BE
 INSTALLED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  