| 2007-11-09 16:12:45 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME CODE SECTIONS FROM PREVIOUS REVIEW |
| | ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE ALSO SEE SEVERAL NEW COMMENTS DUE TO NEW PLANS |
| | BEING SUBMITTED FOR REVIEW. |
| | |
| | 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS |
| | PREVIOUSLY STATED AND REQUIRED BY FBC. |
| | 2004 FBC/W2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE KNOW THAT INFORMATION AND PAPER |
| | DOCUMENTATION MAY NOT BE TAPED ONTO PLANS. |
| | PLEASE COPY AND PRINT SHEETS. |
| | PLEASE BE SURE THE PRINTED NAME AND SIGNATURE OF THE |
| | PERSON TAKING RESPONSIBILITY FOR PLANS IS DONE ON NEW |
| | SHEETS. |
| | FBC 106.1.2, 106.5 |
| | |
| | 3) NOTE: PLEASE SEE PLANS ARE MISSING RECEPTACLES PER |
| | 210.52. |
| | FOR EXAMPLE: WALL SPACES IN KITCHEN. |
| | |
| | 4) NOTE: PLEASE SEE 210.52B1, 210.11C2, 220.53 AS 1500 |
| | VA IS REQUIRED FOR ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. THIS COMMENT IS FOR THE DINIGN ROOM |
| | CIRCUITED. |
| | |
| | 5) NOTE: PANEL SCHEDULE SHOWS JACUZZI TUB GFI CIRCUIT |
| | YET PLANS DO NOT SHOW ANY ELECTRICAL. |
| | THIS IS THE SAME FOR OTHER ITEMS WHICH ARE MISSING |
| | ELECTRICAL OUTLETS/RECEPTACLES ON PLANS. |
| | WASHER, DRYER, DISHWASHER ETC. |
| | PLEASE COMPLETE PLANS WITH ALL ELECTRICAL FOR MINIMUM |
| | NEC COMPLIANCE AND ELECTRICAL WHICH IS LISTED ON PANEL |
| | SCHEDULE. |
| | FBC 106.3.5.4 |
| | |
| | 6) NOTE: PLEASE SEE 210.52D, 210.11C3 AS ALL DEDICATED |
| | BATH RECEPTACLE CIRCUITS SHALL BE 20AMP AND #12 AWG. |
| | PANEL SCHEDULE SHOWS 15AMP BREAKERS. |
| | |
| | 7) NOTE: PLEASE SEE 230.70, AS NO MORE THAN 8FT OF |
| | UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE DWELLING. |
| | PLEASE KNOW AS THIS IS AN EXISTING DWELLING, THESE |
| | WOULD NOT BE IN THE SLAB AND BASED ON LOCATION AND |
| | SCALE ON PLANS, A MAIN WITH OCP WOULD BE REQUIRED |
| | OUTSIDE. |
| | THE OTHER OPTION WOULD BE TO RELOCATE PANEL FROM |
| | LOCATION SHOWN TO DECREASE UNPROTECTED CONDUCTOR |
| | LENGTH. |
| | |
| | 8) NOTE: PLEASE SUBMIT REVISED COMPLETED PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |