2007-11-09 16:12:45** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME CODE SECTIONS FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE SEVERAL NEW COMMENTS DUE TO NEW PLANS
 BEING SUBMITTED FOR REVIEW.
  
 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS
 PREVIOUSLY STATED AND REQUIRED BY FBC.
 2004 FBC/W2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE KNOW THAT INFORMATION AND PAPER
 DOCUMENTATION MAY NOT BE TAPED ONTO PLANS.
 PLEASE COPY AND PRINT SHEETS.
 PLEASE BE SURE THE PRINTED NAME AND SIGNATURE OF THE
 PERSON TAKING RESPONSIBILITY FOR PLANS IS DONE ON NEW
 SHEETS.
 FBC 106.1.2, 106.5
  
 3) NOTE: PLEASE SEE PLANS ARE MISSING RECEPTACLES PER
 210.52.
 FOR EXAMPLE: WALL SPACES IN KITCHEN.
  
 4) NOTE: PLEASE SEE 210.52B1, 210.11C2, 220.53 AS 1500
 VA IS REQUIRED FOR ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. THIS COMMENT IS FOR THE DINIGN ROOM
 CIRCUITED.
  
 5) NOTE: PANEL SCHEDULE SHOWS JACUZZI TUB GFI CIRCUIT
 YET PLANS DO NOT SHOW ANY ELECTRICAL.
 THIS IS THE SAME FOR OTHER ITEMS WHICH ARE MISSING
 ELECTRICAL OUTLETS/RECEPTACLES ON PLANS.
 WASHER, DRYER, DISHWASHER ETC.
 PLEASE COMPLETE PLANS WITH ALL ELECTRICAL FOR MINIMUM
 NEC COMPLIANCE AND ELECTRICAL WHICH IS LISTED ON PANEL
 SCHEDULE.
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE 210.52D, 210.11C3 AS ALL DEDICATED
 BATH RECEPTACLE CIRCUITS SHALL BE 20AMP AND #12 AWG.
 PANEL SCHEDULE SHOWS 15AMP BREAKERS.
  
 7) NOTE: PLEASE SEE 230.70, AS NO MORE THAN 8FT OF
 UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE DWELLING.
 PLEASE KNOW AS THIS IS AN EXISTING DWELLING, THESE
 WOULD NOT BE IN THE SLAB AND BASED ON LOCATION AND
 SCALE ON PLANS, A MAIN WITH OCP WOULD BE REQUIRED
 OUTSIDE.
 THE OTHER OPTION WOULD BE TO RELOCATE PANEL FROM
 LOCATION SHOWN TO DECREASE UNPROTECTED CONDUCTOR
 LENGTH.
  
 8) NOTE: PLEASE SUBMIT REVISED COMPLETED PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  