| Plan Review Notes For Permit 07040545 |
| Permit Number |
07040545 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-27 12:33:43 | BUILDING REVIEW CHECKLIST: | | | 1- ATTACHED LETTER STATES REPLACING THREE EXISTING | | | WINDOWS. NEED TO PROVIDE2 COPIES OF PRODUCT APPROVALS | | | FOR THE WINDOWS AS REQUIRED BY DCA RULE 9B-72. SPECIFY | | | TYPE AND SIZE OF EXISTING WINDOW AND TYPE AND SIZE OF | | | PROPOSED WINDOW TO VERIFY COMPLIANCE WITH EGRESS | | | REQUIREMENTS IF WINDOWS ARE LOCATED IN BEDROOMS. | | | | | | 2- PERMIT APPLICATION CALLS FOR DRYWALL AND INSULATION | | | INSTALLATION. NEED TO PROVIDE THE ENERGY CALCULATIONS | | | AS REQUIRED BY CHAPTER 13 FBC 2004.COMPLETELY FILL | | | OUT BOTH SIDES OF ATTACHED ENERGY CALCULATIONS FORMS. | | | INCLUDING TOP OF FORM AND BOTTOM OF FORM TO BE SIGNED | | | AND DATED ACCORDINGLY. | | | | | | 3- SKETCHES SUBMITTED TO SHOW AREAS WHERE DRYWALL , | | | INSULATION AND WINDOWS AREGOING TO BE INSTALLED. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 4- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION | | | IS TOO LOW.PERMIT VALUATION NEEDS TO INCLUDE ALL | | | MATERIALS AND LABOR FOR ALL THE WORK TO BE PERFORMED, | | | INCLUDING ALL ELECTRICAL AND PLUMBING WORK.UPDATE | | | PERMIT VALUATION AS REQUIRED BY SEC. 108.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|