2007-06-27 12:33:43BUILDING REVIEW CHECKLIST:
 1- ATTACHED LETTER STATES REPLACING THREE EXISTING
 WINDOWS. NEED TO PROVIDE2 COPIES OF PRODUCT APPROVALS
 FOR THE WINDOWS AS REQUIRED BY DCA RULE 9B-72. SPECIFY
 TYPE AND SIZE OF EXISTING WINDOW AND TYPE AND SIZE OF
 PROPOSED WINDOW TO VERIFY COMPLIANCE WITH EGRESS
 REQUIREMENTS IF WINDOWS ARE LOCATED IN BEDROOMS.
  
 2- PERMIT APPLICATION CALLS FOR DRYWALL AND INSULATION
 INSTALLATION. NEED TO PROVIDE THE ENERGY CALCULATIONS
 AS REQUIRED BY CHAPTER 13 FBC 2004.COMPLETELY FILL
 OUT BOTH SIDES OF ATTACHED ENERGY CALCULATIONS FORMS.
 INCLUDING TOP OF FORM AND BOTTOM OF FORM TO BE SIGNED
 AND DATED ACCORDINGLY.
  
 3- SKETCHES SUBMITTED TO SHOW AREAS WHERE DRYWALL ,
 INSULATION AND WINDOWS AREGOING TO BE INSTALLED.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 4- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW.PERMIT VALUATION NEEDS TO INCLUDE ALL
 MATERIALS AND LABOR FOR ALL THE WORK TO BE PERFORMED,
 INCLUDING ALL ELECTRICAL AND PLUMBING WORK.UPDATE
 PERMIT VALUATION AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712