Plan Review Notes
Plan Review Notes For Permit 07040545
Permit Number 07040545
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-05 10:22:52DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: THE SUBMITTED PLUMBING RISER IS NOT A SANITARY
 ISOMETRIC RISER DIAGRAM, DOES NOT REFLECT THE FLOOR
 PLAN AND NOT ALL PIPING IS SIZED. PLEASE REFERENCE THE
 ATTACHED SANITARY ISOMETRIC RISER DIAGRAM TO THE
 PLUMBING COMMENTS THAT IS CODE COMPLIANT AND REFLECTS
 THE FLOOR PLAN FOR THE RESUBMITTAL.
  
 2. PER FBC-2004 PLUMBING, SECTION 1002.1 A FIXTURE
 SHALL NOT BE DOUBLE TRAPPED. A WATER CLOSET HAS AN
 INTREGRAL TRAP THEREFORE A TRAP IS NOT REQUIRED FOR THE
 SANITARY ISOMETRIC RISER DIAGRAM.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 4. PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721