| Date |
Text |
| 2007-05-17 14:43:22 | ** UNSAT ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES |
| | IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK |
| | AS SHOWN. |
| | PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER |
| | 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006 |
| | REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC. |
| | SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD |
| | ALSO BE ON COVER SHEETS. |
| | WE ARE UNDER THE 2005 NFPA-70. (NEC). |
| | PLEASE ALSO LIST THE FOLLOWING. |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING |
| | IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS |
| | TO SHOW MEETING THE CURRENT CODE FOR SMOKE |
| | DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE |
| | EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES |
| | INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A |
| | MULTI-LEVEL BUILDING. |
| | PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON |
| | THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN |
| | NFPA-72 OR CALL TO GO OVER. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR 2005 NEC |
| | COMPLIANCE: |
| | PLEASE COMPLETE RISER WITH ALL MINIMUM CONDUCTOR |
| | SIZES. |
| | PLEASE INDICATE ALL OVER CURRENT PROTECTION DEVICES FOR |
| | SERVICE AND BRANCH CIRCUITS. |
| | PLEASE SUBMIT A COMPLETED PANEL SCHEDULE SHOWING ALL |
| | MINIMUM REQUIRED CIRCUITS AND OTHER DEDICATE CIRCUITS |
| | PER NEC. |
| | PLEASE COMPLETE PLANS WITH ALL ELECTRICAL. |
| | PLEASE COMPLETE KITCHEN LAY OUT. |
| | PLEASE SHOW ALL DISCONNECT LOCATIONS. |
| | PLEASE SUBMIT AIC RATINGS FOR NEW SERVICE EQUIPMENT. |
| | PLEASE COMPLETE CORRECT GROUNDING ELECTRODE SYSTEM. |
| | PLEASE COMPLETE FIXTURE LEGEND AND EGRESS LIGHT. PLEASE |
| | SUBMIT COMPLETED LOAD CALCULATIONS. |
| | PLEASE SEE FBC CHAPTER 13 FOR ENERGY EFFICIENCY |
| | COMPLIANCE FOR ANY RECESSED LIGHTING FIXTURES AND ALSO |
| | FOR A/C WORK ETC. SEE MECH REVIEW COMMENTS. 210.8A, |
| | 210.52,210.11,220, 230, 240, 440,422, 424, 210.70 |
| | 310.16 ETC. |
| | ** PLEASE KNOW THERE ARE TOO MANY ITEMS MISSING FOR A |
| | CODE COMPLIANT REVIEW. PLEASE COMPLETE AS NOT |
| | EVERYTHING AS MENTIONED ABOVE IS ALL REQUIRED PER |
| | MINIMUM CODE. |
| | |
| | 4) NOTE: PLEASE KNOW THAT PLANS MUST BE SUBMITTED IN A |
| | MINIMUM 1/8 SCALE, DRAFTSMAN?S QUALITY, MAY NOT BE IN |
| | PEN OR PENCIL. |
| | MUST CONTAIN PRINTED NAME AND SIGNATURE FROM THE DESIGN |
| | PROFESSIONAL. |
| | FS 481.229, 471.003 |
| | FBC 106.1.3, 106.1.2, 106.3.5.4 |
| | |
| | 5) NOTE:VALUE FOR COMPLETE SCOPE OF WORK MUST INCLUDE |
| | FAIR MARKET VALUE AND INCLUDE ALL LABOR AND MATERIALS |
| | EVEN IF OWNER SUPPLIED AND NO COST FOR LABOR AS OWNER |
| | CONSTRUCTED. |
| | FBC 108.3 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |