| Plan Review Notes For Permit 07040539 |
| Permit Number |
07040539 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-26 12:15:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)THE ENGINEER'S SPECIFICATION REFERS TO TWO | | | DIFFERENT FASTENERS, BUT THE ASSEMBLY SELECTED BY THE | | | CONTRACTOR HAS ONLY ONE FASTENER OPTION.THE | | | ENGINEER'S SPECIFICATION IS IN CONFLICT WITH THE NOA, | | | AND CALCULATIONS FOR THE CHANGE OF FASTENER WAS NOT | | | PROVIDED. | | | | | | 2.)THE SPECIFICATION FOR THE SHINGLES STATES THAT 15* | | | WILL BE INSTALLED.DOUBLE UNDERLAYMENT REQUIRED | | | FBC1507.2.8. | | | | | | |
|