Plan Review Notes
Plan Review Notes For Permit 07040533
Permit Number 07040533
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-02 07:46:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 MUNICIPAL CODE WPB
  
 1. SHT A0.0 NOTE #8. IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5.
  
 2. SHTS P1.0 & P3.0 A GREASE INTERCEPTOR SHALL BE SIZED
 BY ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY
 COMPO, (561) 922-2272 OR CALVIN WILLIAMS, (561)
 722-2284. THEIR FAX NUMBER IS (561) 2287 & E-MAIL'S ARE
 [email protected] OR [email protected].
  
 3. SHTS P2.0 & P4.1 FIXTURE ADL24 & WATER ISOMETRIC
 RISER DIAGRAM. HOT WATER SHALL BE ON THE LEFT SIDE OF
 THE FIXTURE PER SECTION 607.4.
  
 4. SHTS P3.0 & P4.1 THE DISHWASHER SHALL DISCHARGE INTO
 THE SANITARY SYSTEM, NOT THE GREASE SYSTEM PER
 MUNICIPAL CODE SECTION 90-124(7)(B).
  
 5. SHT P4.0 EQUIPMENT AND FIXTURES UTILIZED FOR THE
 STORAGE, PREPARATION AND HANDLING OF FOOD SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP, NOT AN AIR BREAK AS SHOWN IN DETAILS 1 & 8.
 SECTION 802.1.1. THE AIR GAP BETWEEN THE INDIRECT WASTE
 PIPE AND THE FLOOD LEVEL RIM OF THE WASTE RECEPTOR
 SHALL BE A MINIMUM OF TWICE THE EFFECTIVE OPENING OF
 THE INDIRECT WASTE PIPE. SECTION 802.2.1.
  
 6. SHT P4.1 THE WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 7. THE REVERSE OSMOSIS DRINKING WATER TREATMENTS SHALL
 MEET THE REQUIREMENTS OF NSF-58, REVERSE OSMOSIS
 DRINKING WATER TREATMENT UNITS, OR WATER QUALITY
 ASSOCIATION STANDARD S-300, POINT-OF-USE LOW PRESSURE
 REVERSE OSMOSIS DRINKING WATER SYSTEMS. SECTION 611.2.
 PLEASE SUBMIT MANUF SPECIFICATION SHEETS INDICATING
 COMPLIANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved