| Plan Review Notes For Permit 07040533 |
| Permit Number |
07040533 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-04 15:07:52 | --------------DENIED---------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. EF SCHEDULE: ACCESSORY NOTE #3 STATES "INTERLOCK PER | | | EXHAUST FAN NOTES FOR CONTROL." NO SICH INFORMATION | | | COULD BE LOCATED ON PLANS. HOW IS FAN TO BE | | | CONTROLLED? | | | | | | 2. A7.3 SHOWS WARMING OVENS WITH EXHAUST DUCTS. NO | | | INFORMATION COULD BE FOUND ON MECHANICAL PLANS | | | REGARDING THE LOCATION OR TERMINATION OF THIS DUCT. | | | | | | 3. M3.0 ROOF CURB DETAIL STATES "FOR REFERENCE ONLY." | | | WHERE IS THE VERIFICATION FROM STRUCTURAL ENGINEER TO | | | BE FOUND? PROVIDE WIND LOAD CALCS FOR BUILDING PLAN | | | REVIEW. FBC 106.1.2 AND 106.3.5.1.1(8) | | | | | | 4. PLEASE SHOW LAYOUT OF ROOF EQUIPMENT AND ROOF | | | PENETRATIONS TO SHOW COMPLIANCE WITH ALL OF FBC,M | | | 401.5. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805-6719 | | | [email protected] |
|