2007-05-04 15:07:52--------------DENIED----------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. EF SCHEDULE: ACCESSORY NOTE #3 STATES "INTERLOCK PER
 EXHAUST FAN NOTES FOR CONTROL." NO SICH INFORMATION
 COULD BE LOCATED ON PLANS. HOW IS FAN TO BE
 CONTROLLED?
  
 2. A7.3 SHOWS WARMING OVENS WITH EXHAUST DUCTS. NO
 INFORMATION COULD BE FOUND ON MECHANICAL PLANS
 REGARDING THE LOCATION OR TERMINATION OF THIS DUCT.
  
 3. M3.0 ROOF CURB DETAIL STATES "FOR REFERENCE ONLY."
 WHERE IS THE VERIFICATION FROM STRUCTURAL ENGINEER TO
 BE FOUND? PROVIDE WIND LOAD CALCS FOR BUILDING PLAN
 REVIEW. FBC 106.1.2 AND 106.3.5.1.1(8)
  
 4. PLEASE SHOW LAYOUT OF ROOF EQUIPMENT AND ROOF
 PENETRATIONS TO SHOW COMPLIANCE WITH ALL OF FBC,M
 401.5.
  