Plan Review Notes
Plan Review Notes For Permit 07040533
Permit Number 07040533
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-13 11:08:39***DENIED***
  
 1) OUTSIDE SEATING SHALL NOT INTERFERE WITH EXIT
 DISCHARGE FROM BUILDING.
  
 2) IN ADDITION TO THE FLORIDA FIRE PREVENTION CODE
 2004, LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) ADDRESS TO BE A MINIMUM OF 6" IN HEIGHT FOR
 COMMERCIAL BUILDINGS, AND CONTRASTING TO THE
 BACKGROUND. (SHEET A1.0 NOTE #2)
  
 5) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 6) OCCUPANT NOTIFICATION WILL BE REQUIRED IN AREA OF
 DUCT SMOKE DETECTOR(S).
  
 7) KNOX BOX TO BE INSTALLED FOR AFTER HOURS EMERGENCY
 ACCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756