| Plan Review Notes For Permit 07040533 |
| Permit Number |
07040533 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-13 11:08:39 | ***DENIED*** | | | | | | 1) OUTSIDE SEATING SHALL NOT INTERFERE WITH EXIT | | | DISCHARGE FROM BUILDING. | | | | | | 2) IN ADDITION TO THE FLORIDA FIRE PREVENTION CODE | | | 2004, LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 4) ADDRESS TO BE A MINIMUM OF 6" IN HEIGHT FOR | | | COMMERCIAL BUILDINGS, AND CONTRASTING TO THE | | | BACKGROUND. (SHEET A1.0 NOTE #2) | | | | | | 5) PLEASE PROVIDE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING. | | | | | | 6) OCCUPANT NOTIFICATION WILL BE REQUIRED IN AREA OF | | | DUCT SMOKE DETECTOR(S). | | | | | | 7) KNOX BOX TO BE INSTALLED FOR AFTER HOURS EMERGENCY | | | ACCESS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|