Plan Review Notes
Plan Review Notes For Permit 07040533
Permit Number 07040533
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-23 13:07:49 
 *** UNSAT ***
  
 1) NOTE: PLEASE INDICATE THE FOLLOWING CODES ON
 ELECTRICAL PLANS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 ** PLEASE KNOW THAT ANY OTHER CODES FOR OTHER TRADES
 MAY BE REQUIRED.
  
 2) NOTE: PLEASE SEE PLAN NOTES MENTIONS THAT THERE WILL
 BE A * DRIVE-THRU* HOWEVER THIS COULD NOT BE LOCATED ON
 PLANS.?
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE SEE THE LOCATION OF THE SERVICE ON THE
 EAST SIDE OF THE BUILDING CONTAINSA DRIVEWAY/PARKING
 LOT AREA WHICH IS SUBJECT TO TRUCK AND VEHICLE TRAFFIC.
 PLEASE INDICATE THE HEIGHT OF THE RISER AS REQUIRED PER
 230.24B4.
 PLEASE ALSO PLACE A NOTE ON PLANS FOR REQUIRED BOLLARDS
 FOR PROTECTION OF THE SERVICE EQUIPMENT PER 110.26(F)2
  
 4) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THAT
 OF THE ELECTRICAL LIGHTING FIXTURES ON PLANS. PLEASE
 SEE PLANS INDICATE EXTERIOR LIGHTING FIXTURES, YET
 CALCULATIONS DO NOT INDICATE ANY.
 PLEASE SEE THE WATTAGE, TYPES OF FIXTURES ON PLANS DO
 NOT COORDINATE WITH THE ENERGY CALCULATIONS. PLEASE SEE
 13-415.1.AB.1, 13-415.2, PLEASE BE SURE TO SEE
 13-415.2.ABC.1.2 FOR TRACK LIGHTING.
 PLEASE SEE THAT FOUR COPIES WERE SUBMITTED WHEN ONLY
 TWO COPIES ARE NEEDED.
  
 5) NOTE: PLEASE SUBMIT AIC RATING FOR ALL SERVICE
 EQUIPMENT INCLUDING MAIN.
 110.9,
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE GROUNDING ELECTRODE RISER
 MENTIONS CONNECTION TO THE FOOTER STEEL, HOWEVER AS
 THIS IS AN EXISTING BUILDING, FOOTER STEEL MAY OR MAY
 NOT BE AVAILABLE. IN THE INTEREST OF AFFECTING THE
 STRUCTURAL STABILITY OF THE EXISTING FOOTER 250.50 DOES
 NOT REQUIRE ATTACHMENT WHEN THE EXISTING IS NOT
 AVAILABLE.
 PLEASE KNOW THAT IF SHOWN PART OF THE GE SYSTEM ON
 PLANS, CONNECTION WILL BE REQUIRED.
  
 7) NOTE: PLEASE SEE THE RISER IS MISSING THE TAP
 CONDUCTORS FROM THE GUTTER TO PANELS.
 240.21, 408.36, 240.4, 310.16 ETC CAN NOT BE VERIFIED
 AT THIS TIME.
 PLEASE ALSO INDICATE CONDUIT SIZES.
  
 8) NOTE: PLEASE SEE 422.13 FOR WATER HEATER LOADS
 REQUIRED AT 125%.
  
 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS
 AT 125%. 2215.3, 230.42 ETC.
  
 10) NOTE: PLEASE CLARIFY LOADS FOR TRACK LIGHTING AND
 SHOW WINDOWS PER 220.43 A AND B.
  
 11) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 ABOVE WEST WINDOW. MOST WINDOWS ARE SHOWN BUT NOT ALL.
 12) NOTE: ** PLEASE KNOW THAT THE BASE PLANS MAY BE
 USED AS REFERENCE FOR LOW VOLTAGE WORK AS SHOWN HOWEVER
 THE LV SECURITY AND OTHER LV SYSTEMS WILL BE REQUIRED
 TO BE UNDER SEPARATE PERMITS AND FEES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-22 14:47:20REVIEW TO CONTINUE ON 4/23
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETE.