| 2007-04-26 18:09:43 | *****DENIED***** |
| | |
| | |
| | 1.FIRE DEPARTMENT ACCESS ROAD SHALL BE DESIGNED AND |
| | MAINTAINED TO SUPPORT THE IMPOSED LOADS OF FIRE |
| | APPARATUS AND SHALL BE PROVIDED WITH A SURFACE SUITABLE |
| | FOR ALL-WEATHER DRIVING CAPABILITIES. |
| | |
| | 2.DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF |
| | 150 FEET IN LENGHT SHALL BE PROVIDED WITH APPROVED |
| | PROVISIONS FOR TURNING THE APPARATUS AROUND. |
| | |
| | 3.SHOW THE LOCATION OT THE NEAREST FIRE HYDRANT TO |
| | THIS STRUCTURE. |
| | |
| | 4.THE INSTALLATION AND/OR ERECTING OF THE TEMPORARY |
| | STRUCTURE SHALL IN NO WAY HINDER OR OBSTRUCT EMERGENCY |
| | RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY |
| | THEREOF (INCLUDING ROADS, STREETS, AND FIRE LANES). |
| | |
| | 5.THE STRUCTURE SHALL HAVE APPROVED ADDRESS NUMBERS |
| | PLACED IN A POSITION TO BE PLANILY LEGIBLE AND VISIBLE |
| | FROM THE STREET OR ROAD FRONTING THE PROPERTY.AS PER |
| | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS |
| | THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. IN THE |
| | EVENT THAT THE ADDRESS CANNOT BE SEEN FROM EXECUTIVE |
| | CENTER DRIVE (DUE TO THE STRUCTURE'S SET-BACK), A |
| | MARKEE WITH THE ADDRESS WILL BE REQUIRED IN ADDITION TO |
| | THAT ON THE STRUCTURE. |
| | |
| | 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S) FOR THE STRUCTURE. |
| | |
| | 7.NO EMERGENCY LIGHTING NOTED.ALTHOUGH NOT A |
| | REQUIREMENT DUE TO THE SIZE OF THE STRUCTURE, IT IS |
| | RECOMMENDED THAT EMERGENCY LIGHTING BE PROVIDED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS |
| | ADDRESSED. |
| | |
| | |