Plan Review Notes
Plan Review Notes For Permit 07040518
Permit Number 07040518
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-26 18:09:43*****DENIED*****
  
  
 1.FIRE DEPARTMENT ACCESS ROAD SHALL BE DESIGNED AND
 MAINTAINED TO SUPPORT THE IMPOSED LOADS OF FIRE
 APPARATUS AND SHALL BE PROVIDED WITH A SURFACE SUITABLE
 FOR ALL-WEATHER DRIVING CAPABILITIES.
  
 2.DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF
 150 FEET IN LENGHT SHALL BE PROVIDED WITH APPROVED
 PROVISIONS FOR TURNING THE APPARATUS AROUND.
  
 3.SHOW THE LOCATION OT THE NEAREST FIRE HYDRANT TO
 THIS STRUCTURE.
  
 4.THE INSTALLATION AND/OR ERECTING OF THE TEMPORARY
 STRUCTURE SHALL IN NO WAY HINDER OR OBSTRUCT EMERGENCY
 RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY
 THEREOF (INCLUDING ROADS, STREETS, AND FIRE LANES).
  
 5.THE STRUCTURE SHALL HAVE APPROVED ADDRESS NUMBERS
 PLACED IN A POSITION TO BE PLANILY LEGIBLE AND VISIBLE
 FROM THE STREET OR ROAD FRONTING THE PROPERTY.AS PER
 WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. IN THE
 EVENT THAT THE ADDRESS CANNOT BE SEEN FROM EXECUTIVE
 CENTER DRIVE (DUE TO THE STRUCTURE'S SET-BACK), A
 MARKEE WITH THE ADDRESS WILL BE REQUIRED IN ADDITION TO
 THAT ON THE STRUCTURE.
  
 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) FOR THE STRUCTURE.
  
 7.NO EMERGENCY LIGHTING NOTED.ALTHOUGH NOT A
 REQUIREMENT DUE TO THE SIZE OF THE STRUCTURE, IT IS
 RECOMMENDED THAT EMERGENCY LIGHTING BE PROVIDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722