Plan Review Notes
Plan Review Notes For Permit 07040518
Permit Number 07040518
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-21 13:59:50** UNSAT **
  
 1) NOTE: PLEASE STATE ON PLANS ALL UPDATED DATED
 ADOPTED CODES AS OF DECEMBER 8TH, 2006 WHICH MUST
 INCLUDE THE FOLLOWING AT A MINIMUM FOR ELECTRICAL.
 PERMIT APPLICATIONS AFTER THIS DATE FALLS UNDER THE NEW
 CODES.
 NFPA-70 2005, 2004 FBC W/ 2006 REVISIONS.
 1999 CODE SHOWN FOR NEC.
 ** SEE OTHER TRADE REVIEWS FOR ANY OTHER CODES.
  
 2) NOTE: PLEASE SEE PLANS DO NOT INDICATE CODE
 COMPLIANCE FOR THE LOCATION OF THE WATER HEATER OR ANY
 DISCONNECTING MEANS REQUIRED PER 422.30/31.
 PLEASE SEE 422.13 AS THE LOADS MUST BE SHOWN AT 125%
 ALONG WITH THE MINIMUM SIZE OF THE CIRCUIT.
 PLEASE REVISE.
  
 3) NOTE: PLEASE SEE THE ATTACHED ENERGY CALCULATIONS
 CONTAIN A RAISED SEAL OVER A PHOTO-0COPIED SIGNATURE
 WHICH IS NOT PERMITTED UNDER FS 471.025.
 WHEN AN ENGINEER AFFIX?S HIS/HER SEAL TO ANY DOCUMENT,
 THE SIGNATURE AND DATE MUST BE ORIGINAL.
 PLEASE VERIFY THE CODE/METHOD FOR ENERGY CALCULATIONS.
  
  
 4) NOTE: PLEASE PROVIDE AN ELECTRICAL RISER DIAGRAM
 INDICATING THE SERVICE WHICH WILL BE FEEDING THIS NEW
 TRAILER ALONG WITH SERVICE CONDUCTORS, OVER CURRENT
 PROTECTION, MAINS, GROUNDING AT SERVICE AND TRAILER,
 CONDUITS, ETC.
 COMPLETE RISER.
 310.16, 230.70, 230.71, 250.50 ETC.
  
 ** PLEASE SEE ANY FIRE REVIEW COMMENTS FOR REQUIRED
 EMERGENCY LIGHTING WHICH MAY BE REQUIRED PER 2003 LS
 7.8/7.9
 THIS WOULD AFFECT PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]