Plan Review Notes
Plan Review Notes For Permit 07040513
Permit Number 07040513
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-01 12:59:22** PROVISO/REVISION REQUIRED ***
  
 1) NOTE: PLEASE KNOW SINCE THE DATE OF THE PREVIOUS
 REVIEW IT HAS BEEN CONFIRMEDWITH THE STATE OF FLORIDA
 AND BY THE DEFINITIONS SET FORTH IN FBC CHAPTER 13 AND
 FBC, THAT THE METHOD *A* AS SUBMITTED CAN NOT BE USED.
  
 THE CALCULATIONS SUBMITTED ARE FOR *WHOLE BUILDING *
 WHICH THIS TENANT BUILD OUT SPACE IS NOT.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2
 PLEASE KNOW THESE WILL BE REQUIRED BEFORE ANY ROUGH
 ELECTRICAL INSPECTION. LIGHTING LEVELS HAVE NOT BEEN
 CONFIRMED BASED ON USE OF ROOMS OR AREAS AND ANY
 INSTALLATION OF NEW LIGHTING FIXTURES WILL BE *AT RISK*
 UNTIL LIGHTING LEVELS CAN BE CONFIRMED TO COMPLY.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717