| Plan Review Notes For Permit 07040513 |
| Permit Number |
07040513 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-10-01 12:59:22 | ** PROVISO/REVISION REQUIRED *** | | | | | | 1) NOTE: PLEASE KNOW SINCE THE DATE OF THE PREVIOUS | | | REVIEW IT HAS BEEN CONFIRMEDWITH THE STATE OF FLORIDA | | | AND BY THE DEFINITIONS SET FORTH IN FBC CHAPTER 13 AND | | | FBC, THAT THE METHOD *A* AS SUBMITTED CAN NOT BE USED. | | | | | | THE CALCULATIONS SUBMITTED ARE FOR *WHOLE BUILDING * | | | WHICH THIS TENANT BUILD OUT SPACE IS NOT. | | | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER | | | 13-415.2 | | | PLEASE KNOW THESE WILL BE REQUIRED BEFORE ANY ROUGH | | | ELECTRICAL INSPECTION. LIGHTING LEVELS HAVE NOT BEEN | | | CONFIRMED BASED ON USE OF ROOMS OR AREAS AND ANY | | | INSTALLATION OF NEW LIGHTING FIXTURES WILL BE *AT RISK* | | | UNTIL LIGHTING LEVELS CAN BE CONFIRMED TO COMPLY. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 |
|