| 2007-08-05 11:02:13 | --------------DENIED----------------- |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS |
| | FBC CH. AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 2ND REVIEW: |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTNUITY. |
| | |
| | 1. FIRE DAMPERS ARE TO BE INSTALLED IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF FBC,M SEC 607 AND THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS AND LISTING. |
| | ALSO, PLAN INDICATES 6 INCH ROUND FLEX DUCT ATTACHING |
| | TO FIRE DAMPER AT NEW TENANT SEPARATION WALL. THIS |
| | SCENARIO IS NOT ADDRESSED IN INSTALLATION DETAIL AS |
| | SHOWN ON PLANS AND IS LIKELY NOT ALLOWED PER |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALSO, THIS |
| | WOULD NOT ALLOW FOR A DUCT ACCESS DOOR AS REQUIRED PER |
| | FBC,M 607.4. PLEASE CLARIFY HOW THIS DAMPER IS TO BE |
| | INSTALLED AND CONNECTED TO DUCT IN A MANNER WHICH IS IN |
| | COMPLIANCE WITH FIRE DAMPER INSTALLATION ISTRUCTIONS |
| | AND THIS SECTION OF THE CODE. |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | 4. OK |
| | |
| | 5. MANUFACTURER'S INSTALLATION INSTRUCTIONS WERE |
| | REQUESTED ON PREVIOUS REVIEW. HOWEVER, THEY WERE NOT |
| | PROVIDED WITH THIS SUBMITTAL. PLEASE PROVIDED ALL |
| | REQUESTED SUPPORTING DOCUMENTATION FOR REVIEW WITH NEXT |
| | SUBMITTAL PER FBC 106.1.1 THROUGH 106.1.3. |
| | |