| 2007-08-01 11:11:06 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS |
| | WITH RESPECT TO CHANGES MADE TO PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE |
| | E1.2 FOR NOTES PERTAINING TO ADA LEVELS FOR HORNS AND |
| | STROBES, HOWEVER ONLY A NOTE FOR THE DB LEVELS COULD BE |
| | LOCATED ON THIS PAGE. |
| | PLEASE SEE THE SYMBOL LEGEND DOES CONTAIN THE LEVELS OF |
| | 75 CD FOR THE STROBES, HOWEVER ALSO STATES UNLESS OTHER |
| | WISE NOTED. PLEASE VERIFY IF INDEED THERE WAS GOING TO |
| | BE A NOTE PLACE ON E1.2 FOR CD LEVELS? |
| | FBC 11-4.28.1, .2 AND .3(4) FOR ANY FA DEVICES FOR ADA |
| | COMPLIANCE WHICH MAY BE REQUIRED TO BE CHANGED OR |
| | INSTALLED. |
| | |
| | 3) NOTE: PLEASE SEE THERE ARE A FEW *SEPARATE SPACES* |
| | AND WHAT APPEARS AS ACCENT LIGHTING IN ONE ROOM. PLEASE |
| | SEE REDLINED PLANS. 13-415.1.ABC.1.1, .1.2, .1.3. |
| | PLEASE SEE SOME OF THESE DEVICES ARE STILL BEING SHOWN |
| | AS STANDARD SWITCHES. |
| | PLEASE BE SURE THE *OWNER AGENT* IS SIGNED AND DATED ON |
| | THE CERTIFICATIONS SHEET OF THE ENERGY CALCULATIONS AS |
| | SUBMITTED. |
| | 13-103.1.1.1.1. |
| | |
| | 4) NOTE:PLEASE SEE THE RISER HAS NOW CHANGED. PLEASE |
| | SEE THE RISER NOW SHOWS TAPPED CONDUCTORS FOR THE |
| | 200AMP MAIN. PLEASE SEE THE LOCATION OF THE PANELS |
| | WHICH THE TAPPED CONDUCTORS ARE FEEDING EXCEED THE |
| | DISTANCE PERMITTED OF TAPPED CONDUCTORS PER 240.21. |
| | PLEASE ALSO SEE THAT ANY TAPPED CONDUCTORS MUST |
| | TERMINATE IN OVER CURRENT PROTECTION ALSO AS REQUIRED |
| | IN 240.21. |
| | THESE PANELS ARE BOTH SHOWN AS MLO AND DO NOT CONTAIN |
| | OCP AND ARE TOO FAR WAY. |
| | PLEASE SEE 240.4, 310.16, AND 240.21 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE:PLEASE KNOW THAT CLARIFICATION IS STILL |
| | NEEDED ON THE *TELCO* ROOM. RESPONSE LETTER MENTIONS |
| | THIS IS NOT CONSIDERED AS IT IS A SINGLE TENANT HOWEVER |
| | THE CLASSIFICATIONS ARE BASED ON SEVERAL OTHER FACTORS |
| | IN NFPA-75 AND NEC 645. |
| | PLEASE PROVIDE MORE INFORMATION ON EQUIPMENT WHICH IS |
| | BEING INSTALLED IN ROOM. |
| | PLEASE SEE THE DISCONNECTING MEANS WHICH WAS ADDED TO |
| | THE AC EQUIPMENT HOWEVER 645 REQUIRES A CERTAIN TYPE OF |
| | SHUT OFF. PLEASE ALSO CLARIFY THE DISCONNECTING MEANS |
| | WHICH MAY BE REQUIRED FOR THE OTHER OUTLETS WHICH FEEDS |
| | UNKNOWN EQUIPMENT AT THIS TIME. |
| | PLEASE KNOW THAT THE ROOM MAY BE REQUIRED TO CONTAIN A |
| | MINIMUM RATING OF 1HR IF APPLICABLE. |
| | |
| | ** PREVIOUS NOTE FOR REFERENCE ONLY.** |
| | PLEASE SEE PLANS INDICATE A NEW *TELCO* ROOM WITH NEW |
| | DEDICATED A/C BEING INSTALLED FOR THIS ROOM. 645.4, |
| | 645.5 ETC. |
| | PLEASE CLARIFY USE AND NFPA-75 FOR IT ROOMS AND |
| | REQUIRED DISCONNECTING MEANS FOR EQUIPMENT PER 645.10? |
| | WHAT EQUIPMENT WILL BE LOCATED IN THIS ROOM? |
| | RISK CONSIDERATIONS PER CHAPTER 2 OF NFPA-75 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-31 20:26:22 | IN ELEC FOR REVIEW |