| Plan Review Notes For Permit 07040513 |
| Permit Number |
07040513 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-02 08:25:06 | -------------DENIED-------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | FBC CHAPTER 1 AS AMENDED BY THE CITY OF WEST PALM | | | BEACH | | | | | | | | | 1. PLEASE SHOW DUCTS WHICH WILL PENETRATE NEW TENANT | | | SEPARATION WALL TO BE PROTECTED BY FIRE DAMPERS OR AN | | | APPROVED THROUGH-PENETRATION FIRESTOP SYSTEM (SEE FBC | | | 712.3.3) IN ACCORDANCE WITH FBC,M 607 5.3. | | | | | | 2. RETURN GRILL ON SCHEDULE CALLS FOR NOTE (10) BUT | | | NOTE (10) IS NOT GIVEN ON PLAN. PLEASE CLARIFY. | | | | | | 3. SPLIT SYSTEM SCHEDULE: AHU-T/CU-T CALLS FOR NOTES | | | (1)(2)(3). ONLY NOTE (1) IS GIVEN. PLEASE CLARIFY. | | | | | | 4. THREE FIRE DAMPERS WHICH APPEAR ON DEMOLITION PLAN | | | DO NOT APPEAR ON NEW PLAN. PLEASE COORDINATE DRAWINGS, | | | SHOWING ALL ITEMS TO BE REMOVED ON DEMOLITION PLAN. | | | | | | 5. PLEASE PROVIDE INSTALLATION INSTRUCTIONS FOR | | | MINI-SPLIT SYSTEM SHOWING MAXIMUM ALLOWED LENGTH AND | | | REQUIRED SIZE OF COPPER LINES. ALSO PLEASE VERIFY | | | MAXIMUM ALLOWED ELEVATION DIFFERENCE BETWEEN AHU AND | | | CU. PLEASE SHOW LOCATION/ROUTING OF REFRIGERANT LINES | | | FROM SPACE TO ROOF. FBC 106.1.1, FBC 106.1.3 | | | | | | REVIEWED BY: RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|