2007-04-22 08:32:23** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES TO CHAPTER 1 OF THE FBC
 ARE THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
  
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THIS
 WOULD INCLUDE REQUIRED CODES ON TRADE SHEETS. PLEASE
 KNOW THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT
 DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR ANY
 FA DEVICES FOR ADA COMPLIANCE WHICH MAY BE REQUIRED TO
 BE CHANGED OR INSTALLED.
 PLEASE SEE REVIEWS FROM OTHER TRADES,( FIRE MARSHAL) IF
 ANY WORK TO THESE EXISTING SYSTEMS ARE TAKING PLACE,
 THIS BASE INFORMATION SHALL BE INCLUDE ON THESE BASE
 PLANS EVEN WHEN THESE SYSTEMS ARE UNDER SEPARATE
 PERMIT.
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE SEE 13-101.
 PLEASE SEE MANY SEPARATE SPACE AREAS DO NOT INDICATE
 ANY REQUIRED LIGHTING CONTROL PER 13-415.1.ABC.1.1,
 .1.2.
 PLEASE INDICATE TIMES ON ALL DEVICES BEING USED TO
 CONTROL OR OVER RIDE LIGHTING. PLEASE SEE SOME OF THE
 DEVICES AS SHOWN ARE OK, HOWEVER PLEASE ALSO INDICATE
 TIMES ON SYMBOL LEGEND FOR SPECIFIC DEVICE.(TIME AS
 NOTED ON 2.1 DETAIL)
 PLEASE CLARIFY FIXTURES, AS PLANS SHOW THAT THESE ARE
 NEW TO BE INSTALLED, HOWEVER NO INFORMATION FOR TYPE,
 WATTAGE ETC IS SHOWN. PLEASE SEE 13-415.1.ABC.3. ONE
 NOTE ON PLANS MENTIONS TO RE-LAMP EXISTING AND TO SEE
 THE FIXTURE SCHEDULE FOR DETAILS, HOWEVER NO FIXTURE
 SCHEDULE ETC WAS SUBMITTED TO VERIFY COMPLIANCE. PLEASE
 INDICATE THE NUMBER OF FIXTURES IN THE FIXTURE LEGEND
 FOR EACH AND COORDINATE WITH THE PERFORMANCE
 CALCULATIONS WHICH ARE TO BE SUBMITTED.
 FBC CHAPTER 13, 13-415.2, 13-415.1.AB.1.1, 13-415.1.C ?
 ETC
  
 4) NOTE:PLEASE SEE PERMIT APPLICATION IS ONLY FOR
 TENANT SPACE 212, HOWEVER ELECTRICAL RISER SHOWS WORK
 FOR SPACE 220, OR RATHER SOME OF THE ELECTRICAL FEEDING
 SPACE 220 BEING LOCATED IN THIS TENANT SPACE WHICH IS
 NOT PERMITTED.
 PLEASE ALSO SEE THE TITLE BLOCKS INDICATE UNIT/SUITE
 #20? (MISPRINT)
 PLEASE SEE AS PERMIT APPLICATION IS FOR SUITE #212 AND
 PLANS INDICATE 210, 20 AND 220, LOCATION FOR SCOPE IS
 NOT CLEAR.
 PLEASE CLARIFY SERVICE.
 IF THIS WAS TWO TENANT SPACES BEING MADE INTO ONE, THEN
 ONLY ONE METER WILL BE PERMITTED AND SERVICE WILL BE
 FROM ONE METER ONLY.
 PLEASE SEE THE LOCATIONS OF THE TRANSFORMERS ARE NOT
 SHOWN TO VERIFY COMPLIANCE FOR SPACE INSTALLATIONS PER
 450.9, 450.13, 110.26, ETC.
 CAN NOT VERIFY TAPS PER 240.21
 PLEASE SEE THE #8 AS SHOWN ARE NOT OF SUFFICIENT SIZE
 FOR THE 60AMP DISCONNECTS AND OVER CURRENT PROTECTION
 AS SHOWN.240.4, 310.16, 110.14
 PLEASE SEE THAT RISER MAY BE CHANGING AS COMPLETE SCOPE
 OF WORK ETC IS NOT CLEAR AT THIS TIME.
  
 5) NOTE: PLEASE SEE PLANS INDICATE A NEW *TELCO* ROOM
 WITH NEW DEDICATED A/C BEING INSTALLED FOR THIS ROOM.
 645.4, 645.5 ETC.
 PLEASE CLARIFY USE AND NFPA-75 FOR IT ROOMS AND
 REQUIRED DISCONNECTING MEANS FOR EQUIPMENT PER 645.10?
 WHAT EQUIPMENT WILL BE LOCATED IN THIS ROOM?
 RISK CONSIDERATIONS PER CHAPTER 2 OF NFPA-75
  
  
 ** PLEASE PROVIDE MORE DETAIL AS THERE ARE SOME ITEMS
 NOT CLEAR AT THIS TIME ON PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]