| 2007-08-27 09:15:19 | REVISION DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **OK** RESPONSE NOTED (SHEET P-1.01) |
| | |
| | 2. **NO** SANITARY AND WATER RISER DIAGRAMS ARE |
| | REQUIRED AND SHOULD NOT BE DELETED. (SHEET P-1.01) |
| | NOTE: THE RESUBMITTED REVISION MUST REFLECT THE FIELD |
| | CHANGES, THEY CAN NOT BE DELETED. PER FBC-2004 CHAPTER |
| | 1, SECTION 106.3.5.1.3 PLUMBING (3), (4) (10) AND (13). |
| | PLEASE CORRECT AND RESUBMIT. |
| | |
| | 3. **NO/OK** IS THE INSTA HOT BEING DELETED? IF SO |
| | ELECTRICAL REVISION REQUIRED. (SHEET P-1.01) |
| | NOTE: THE RESUBMITTED PLANS INDICATE THE INSTA HOT |
| | BEING RELOCATED ABOVE CEILING. THE RESUBMITTED REVISED |
| | WATER RISER DIAGRAM NEEDS TO REFLECT THIS. PLEASE |
| | CORRECT AND RESUBMIT. |
| | |
| | 4. PLEASE CLOUD ALL CHANGES AND PROVIDE REVISION |
| | NUMBERS AND DATES ON THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |