| Plan Review Notes For Permit 07040505 |
| Permit Number |
07040505 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-25 15:14:46 | DENIED; | | | 1. DETAILS REQUIRED FOR BREAK SINK AND DRINKING | | | FOUNTAIN. | | | A) BREAK SINK SHALL COMPLY WITH FBC-2004 | | | BUILDING CHAPTER 11, SECTIONS 11-4.24.1 THRU .7 SHOW | | | ALL MESSUREMENT REQUIRED. MUST BE A FRONTAL APPROACH. | | | SHOW CLEAR FLOOR SPACE ON FLOOR PLAN. | | | B) DRINKING FOUNTAIN TO COMPLY WITH SECTIONS | | | 11-4.15.1 THRU .5 | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 805-6695 |
|