| Plan Review Notes For Permit 07040505 |
| Permit Number |
07040505 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-24 15:55:29 | *****DENIED***** | | | | | | | | | 1. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2. UNLESS IT IS WALL RECESSED, RELOCATE THE PLACEMENT | | | OF THE FIRE EXTINGUISHER FROM THE EXTERIOR WALL OF THE | | | MACHINE ROOM AS TO NOT INTRUDING IN THE PATH OF THE | | | EXIT ACCESS CORRIDOR. | | | | | | 3. BE SPECIFIC IN IDENTIFYING THE MINIMUM INTERIOR | | | FINISH FOR WALLS AND CEILINGSIN THE EXITS, EXIT | | | ACCESS CORRIDORS, AND OTHER SPACES AS CLASS A, CLASS B, | | | OR CLASS C. | | | | | | 4.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT | | | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM. | | | | | | 5.IF THE FIRE ALARM SYSTEM IS MODIFIED DUE TO THE | | | SCOPE OF WORK BEING CONDUCTED, SEPARATE PLANS AND | | | PERMIT WILL BE REQUIRED. | | | | | | 6.ON PLAN SHEET E-2.01 INDICATES AN ACCESS CONTROL | | | DOOR.WILL EGRESS THROUGH THIS DOOR BE IMPACTED? | | | PLEASE BE ADVISED THAT DOORS IN THE MEANS OF EGRESS | | | SHALL BE PERMITTED TO BE EQUIPPED WITH AN APPROVED | | | ENTRANCE AND EGRESS ACCESS CONTROL SYSTEM PROVIDED THAT | | | THE CRITERIA OF NFPA 101 CHAPTER 7.2.1.6.2 ARE MET. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|