| 2007-04-27 15:14:52 | ** UNSAT ** |
| | |
| | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE MISSING AIC RATINGS FOR NEW SERVICE |
| | EQUIPMENT, MAINS, PANELS AND BREAKERS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | 110.9 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE |
| | DEVICES. IF THE SMOKE DEVICES ARE 120V WHICH DETECT, |
| | SOUND AN ALARM AND ARE WIRED INLINE, THEN THESE DEVICES |
| | WOULD BE INDICATED AS SA FOR SMOKE ALARMS. PLEASE |
| | ADJUST. |
| | PLEASE KNOW IF THEY ARE INDEED SMOKE DETECTORS PLEASE |
| | INDICATE THE SOUNDING DEVICES. |
| | PLEASE SEE THE MISSING SMOKE DEVICE REQUIRED AT THE |
| | FIRST FLOOR LEVEL LEADING TO THE FLOOR ABOVE. |
| | NFPA-72 11.5.1.1.1, 11.8.3 |
| | |
| | 4) NOTE: PLEASE SEE 210.8A7 WHICH REQUIRES ALL |
| | RECEPTACLES LOCATED WITHIN 6FT OF SINKS TO BE GFI/GFI |
| | PROTECTED EVEN IF THEY ARE SINGLE DEDICATED POINT OF |
| | USE RECEPTACLES. THIS IS REQUIRED FOR 120V DEVICES. |
| | |
| | 5) NOTE: PLEASE CORRELATE THE RISER AND PLANS AS THE |
| | PLANS SEEM TO INDICATE A SEPARATE METER AND MAIN |
| | DISCONNECT. |
| | 106.1.2 |
| | |
| | 6) NOTE:PLEASE SEE 210.12 FOR REQUIRED ARC FAULT |
| | PROTECTION. PLAN NOTE MENTIONS FOR RECEPTACLES, WHICH |
| | CHANGED IN THE 2002 NEC TO REQUIRE ALL OUTLETS IN |
| | BEDROOM/SLEEPING ROOMS TO REQUIRED AFCI PROTECTION. |
| | THIS CHANGED IN THE 2002 AND IS THE SAME IN THE 2005. |
| | ** PLEASE SEE PANEL SCHEDULE(S) ONLY INDICATE ONE AFCI |
| | PROTECTED CIRCUIT WHICH IS NOT POSSIBLE. |
| | |
| | 7) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM PER 250.50. |
| | |
| | 8) NOTE: PLEASE SEE 110.26 FOR THE MINIMUM CLEARANCE |
| | REQUIRED FOR DISCONNECTS SHOWN BEHIND A/C CU. |
| | |
| | 9) NOTE: PLEASE CLARIFY DINING ROOM/BREAKFAST AREA |
| | CIRCUIT(S) AND THE LIKE AS REQUIRED PER 210.52B1, |
| | 210.11C1, 220.52 |
| | |
| | 10) NOTE: PLEASE SEE SOME ROOMS WHICH INDICATE A |
| | SWITCH, BUT IT IS NOT SHOWN FEEDING ANYTHING. |
| | PLEASE ALSO SEE ROOMS WHERE ONLY A J-BOX IS SHOWN FOR A |
| | FAN WILL REQUIRE A LIGHT FIXTURE OF SOME TYOE FOR FINAL |
| | OR A SWITCHED RECEPTACLE WILL BE REQUIRED PER 210.70. |
| | LS 101 7.8 |
| | PLEASE SEE SWITCHES WHICH ARE TIED TO WHAT IS SHOWN A |
| | 3-WAY SWITCHING HOWEVER THE SWITCH IS NOT SHOWN AS A |
| | 3-WAY SWITCH. |
| | |
| | 11) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND |
| | PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS |
| | AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR |
| | EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM |
| | COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT* |
| | ETC IS NOT ACCEPTABLE. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 12) NOTE: PLEASE SEE MISSING GFI RECEPTACLES ALONG |
| | KITCHEN COUNTER SPACES PER 210.52C1-5, 210.8A6. |
| | PLEASE SEE PENINSULAR AND AREA SEPARATED BY SINK. |
| | |
| | 13) NOTE: PLEASE SEE THE LIGHT IN CLOSET DOES NOT MEET |
| | THE MINIMUM CLEARANCES PER 410.8 |
| | |
| | 14) NOTE: PLEASE SEE 422.13 AS THE LOADS SHALL BE SHOWN |
| | AT 125%. |
| | |
| | 15) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OVER |
| | CURRENT PROTECTION FOR THE AHU #2. THIS IS SHOWN AT |
| | 10KW W/ A 2-POLE 20AMP. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |