Plan Review Notes
Plan Review Notes For Permit 07040469
Permit Number 07040469
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-04-20 14:00:18***DENIED***
  
 1) DRAWINGS SHALL COMPLY WITH FBC 106.1.1. PLEASE
 PROVIDE MORE INFORMATION REGARDING PROPERTY TO BE
 PROTECTED, SQUARE FOOTAGE, OCCUPANCY TYPE ETC.
  
 2) IT WOULD APPEAR THAT FIRE ALARM WILL BE SUPERVISING
 AN EXISTING SPRINKLER SYSTEM. NEW FIRE ALARM SYSTEMS
 THAT SUPERVISE AN AUTOMATIC FIRE SPRINKLER SYSTEM SHALL
 BE UL CERTIFIED FOR CENTRAL STATION SERVICE.
  
 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE.
  
 4) DRAWINGS ILLUSTRATE A SMOKE DETECTOR NEAR THE FRONT
 ENTRANCE. PLEASE CLARIFY IF THIS IS THE LOCATION OF
 FACP AS IT IS NOT IDENTIFIED AS SUCH.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW