| Plan Review Notes For Permit 07040469 |
| Permit Number |
07040469 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-20 14:00:18 | ***DENIED*** | | | | | | 1) DRAWINGS SHALL COMPLY WITH FBC 106.1.1. PLEASE | | | PROVIDE MORE INFORMATION REGARDING PROPERTY TO BE | | | PROTECTED, SQUARE FOOTAGE, OCCUPANCY TYPE ETC. | | | | | | 2) IT WOULD APPEAR THAT FIRE ALARM WILL BE SUPERVISING | | | AN EXISTING SPRINKLER SYSTEM. NEW FIRE ALARM SYSTEMS | | | THAT SUPERVISE AN AUTOMATIC FIRE SPRINKLER SYSTEM SHALL | | | BE UL CERTIFIED FOR CENTRAL STATION SERVICE. | | | | | | 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE. | | | | | | 4) DRAWINGS ILLUSTRATE A SMOKE DETECTOR NEAR THE FRONT | | | ENTRANCE. PLEASE CLARIFY IF THIS IS THE LOCATION OF | | | FACP AS IT IS NOT IDENTIFIED AS SUCH. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|