Plan Review Notes
Plan Review Notes For Permit 07040466
Permit Number 07040466
Review Stop E
Sequence Number 5
Notes
Date Text
2008-03-20 15:24:56** DENIEDREVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS BELOW ARE STILL THE SAME AS
 PREVIOUSLY NOTED. SOME COMMENTS ARE NEW AS THE SERVICE
 RISER FOR PROPOSED ELECTRICAL HAS CHANGED.
  
  
  
  
 1) NOTE: PLEASE SEE NO MEANS OF DISCONNECT FOR FEEDERS
 FROM THE GENERATOR AT THE BUILDING MEETING
 225.31-225.39
 THE ATS SHOWN WHICH IS NOTED AS EXISTING DOES NOT SHOW
 UP IN ANY RECORDS GOING BACK IN A SEARCH FOR MANY
 YEARS. THERE IS NOT INFORMATION ON WHETHER OR NOT
 PERMIT WAS EVER APPLIED OR ISSUED FOR THE INSTALLATION
 OF THIS ATS.
 THE ATS AS SHOWN NEEDS MANUFACTURES /SPECS OR CUT
 SHEETS SHOWING COMPLIANCE.
  
 2) NOTE: PLEASE SEE THE CONDUCTORS FROM THE ATS ARE
 SHOWN AS TAPPED CONDUCTOR AS NO OVER CURRENT PROTECTION
 CAN BE VERIFIED. THE ONLY OCP SHOWN IS 400AMPS, IF THIS
 IS THE SAME OCP THAT FEEDS THE MDP THEN PLEASE
 CLARIFY.
 THE J-BOX AS SHOWN DOES NOT CLEARLY SHOW HOW THIS
 WIRING IS BEING DONE AND IT IS NOT EASILY DETERMINED IF
 THERE ARE TAPPED CONDUCTORS WHICH ARE TERMINATING IN
 OCP OR IF THE ATS FEEDS ONLY THE MDP?
 240.4, 310.16, 240.21 ETC.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 INCREASED SCOPE OF WORK AND APPLIED VALUE FOR THE
 COMPLETE SCOPE OF WORKS NEEDS ADJUSTING. THE VALUE IS
 TO INCLUDE ALL WORK, ALL MATERIALS; ALL DESIGN COSTS,
 ALL EQUIPMENT, EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 PLEASE SEE FBC 108.3 AND VERIFY.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  