| 2008-03-20 15:24:56 | ** DENIEDREVIEW ** |
| | |
| | |
| | ** PLEASE SEE SOME COMMENTS BELOW ARE STILL THE SAME AS |
| | PREVIOUSLY NOTED. SOME COMMENTS ARE NEW AS THE SERVICE |
| | RISER FOR PROPOSED ELECTRICAL HAS CHANGED. |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE NO MEANS OF DISCONNECT FOR FEEDERS |
| | FROM THE GENERATOR AT THE BUILDING MEETING |
| | 225.31-225.39 |
| | THE ATS SHOWN WHICH IS NOTED AS EXISTING DOES NOT SHOW |
| | UP IN ANY RECORDS GOING BACK IN A SEARCH FOR MANY |
| | YEARS. THERE IS NOT INFORMATION ON WHETHER OR NOT |
| | PERMIT WAS EVER APPLIED OR ISSUED FOR THE INSTALLATION |
| | OF THIS ATS. |
| | THE ATS AS SHOWN NEEDS MANUFACTURES /SPECS OR CUT |
| | SHEETS SHOWING COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE SEE THE CONDUCTORS FROM THE ATS ARE |
| | SHOWN AS TAPPED CONDUCTOR AS NO OVER CURRENT PROTECTION |
| | CAN BE VERIFIED. THE ONLY OCP SHOWN IS 400AMPS, IF THIS |
| | IS THE SAME OCP THAT FEEDS THE MDP THEN PLEASE |
| | CLARIFY. |
| | THE J-BOX AS SHOWN DOES NOT CLEARLY SHOW HOW THIS |
| | WIRING IS BEING DONE AND IT IS NOT EASILY DETERMINED IF |
| | THERE ARE TAPPED CONDUCTORS WHICH ARE TERMINATING IN |
| | OCP OR IF THE ATS FEEDS ONLY THE MDP? |
| | 240.4, 310.16, 240.21 ETC. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | INCREASED SCOPE OF WORK AND APPLIED VALUE FOR THE |
| | COMPLETE SCOPE OF WORKS NEEDS ADJUSTING. THE VALUE IS |
| | TO INCLUDE ALL WORK, ALL MATERIALS; ALL DESIGN COSTS, |
| | ALL EQUIPMENT, EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. |
| | PLEASE SEE FBC 108.3 AND VERIFY. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |