2007-12-03 15:20:29 
 ** DENIED 4TH TIME **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES BASED ON REVISED PLAN SUBMITTED.
  
  
  
 1) NOTE:ALL CODES BELOW ARE TO BE STATED ON PLANS.
 AS STATED ON PREVIOUS REVIEWS: PLEASE INCLUDE THE
 RELEVANT CODES AS ADOPTED BY FS 553.73.
 PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
 ** PLEASE SEE CODES FROM OTHER TRADES.
 ** PLEASE KNOW THAT THE *LATEST EDITION* IS NOT
 SUFFICIENT.
  
 2) NOTE: PLEASE SEE THE 2005 NEC AS THE RISER AS SHOWN
 IS NON-CODE COMPLIANT AND CONFUSING.
 PLEASE SEE FOR EXAMPLE THE METER WHICH IS NOT ONLY ON
 THE LOAD SIDE OF THE 1200AMP MAIN, BUT ALSO SHOWS
 CONDUITS FROM THE METER TO BOTH THE ATS AND TO MDP. HOW
 IS THIS POSSIBLE?
 PLEASE SEE RISER IS NOT COMPLETE WITH ALL OVER CURRENT
 PROTECTION AND CONDUCTOR SIZES AS NEEDED FOR CODE
 COMPLIANCE REVIEW.
 PLEASE GO OVER RISER AND SUBMIT CORRECTED PLANS.
 240.4, 310.16, ETC
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE SEE RISER IS STILL MISSING *EQUIPMENT
 GROUNDING CONDUCTORS* AS PREVIOUSLY REQUESTED AND
 REQUIRED BY CODE AFTER THE FIRST MEANS OF DISCONNECT.
 250.122, 250.110, 250.24, ETC.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES AS THE INTENDED
 LOADS ARE REQUIRED TO BE SHOWN. NO PANELS , SCHEDULES
 ETC.
 LOAD AS SHOWN IS NOT COMPLETE.
 702.5
  
 5) NOTE: PLEASE SPECIFY IF THERE ARE AN LIFE SAFETY OR
 EMERGENCY LOADS PER 700 PR 701 BEING FED.
  
 6) NOTE: PLEASE SEE PLANS SHOWING A LAYOUT OF ALL
 EQUIPMENT INCLUDING SERVICE EQUIPMENT AND DISCONNECTS
 WERE NOT SUBMITTED. UNABLE TO REVIEW FOR 225.31-225.39
 AT THIS TIME.
  
 7) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 HAS NOT CHANGED PER FBC 108.3.
 ALL EQUIPMENT, LABOR, MATERIALS, DESIGN COST ETC EVEN
 IF *ANY* IS OWNER SUPPLIED SHALL BE INCLUDED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.