| 2007-12-03 15:20:29 | |
| | ** DENIED 4TH TIME ** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW |
| | NOTES BASED ON REVISED PLAN SUBMITTED. |
| | |
| | |
| | |
| | 1) NOTE:ALL CODES BELOW ARE TO BE STATED ON PLANS. |
| | AS STATED ON PREVIOUS REVIEWS: PLEASE INCLUDE THE |
| | RELEVANT CODES AS ADOPTED BY FS 553.73. |
| | PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED |
| | ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | ** PLEASE SEE CODES FROM OTHER TRADES. |
| | ** PLEASE KNOW THAT THE *LATEST EDITION* IS NOT |
| | SUFFICIENT. |
| | |
| | 2) NOTE: PLEASE SEE THE 2005 NEC AS THE RISER AS SHOWN |
| | IS NON-CODE COMPLIANT AND CONFUSING. |
| | PLEASE SEE FOR EXAMPLE THE METER WHICH IS NOT ONLY ON |
| | THE LOAD SIDE OF THE 1200AMP MAIN, BUT ALSO SHOWS |
| | CONDUITS FROM THE METER TO BOTH THE ATS AND TO MDP. HOW |
| | IS THIS POSSIBLE? |
| | PLEASE SEE RISER IS NOT COMPLETE WITH ALL OVER CURRENT |
| | PROTECTION AND CONDUCTOR SIZES AS NEEDED FOR CODE |
| | COMPLIANCE REVIEW. |
| | PLEASE GO OVER RISER AND SUBMIT CORRECTED PLANS. |
| | 240.4, 310.16, ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE RISER IS STILL MISSING *EQUIPMENT |
| | GROUNDING CONDUCTORS* AS PREVIOUSLY REQUESTED AND |
| | REQUIRED BY CODE AFTER THE FIRST MEANS OF DISCONNECT. |
| | 250.122, 250.110, 250.24, ETC. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS NOTES AS THE INTENDED |
| | LOADS ARE REQUIRED TO BE SHOWN. NO PANELS , SCHEDULES |
| | ETC. |
| | LOAD AS SHOWN IS NOT COMPLETE. |
| | 702.5 |
| | |
| | 5) NOTE: PLEASE SPECIFY IF THERE ARE AN LIFE SAFETY OR |
| | EMERGENCY LOADS PER 700 PR 701 BEING FED. |
| | |
| | 6) NOTE: PLEASE SEE PLANS SHOWING A LAYOUT OF ALL |
| | EQUIPMENT INCLUDING SERVICE EQUIPMENT AND DISCONNECTS |
| | WERE NOT SUBMITTED. UNABLE TO REVIEW FOR 225.31-225.39 |
| | AT THIS TIME. |
| | |
| | 7) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK |
| | HAS NOT CHANGED PER FBC 108.3. |
| | ALL EQUIPMENT, LABOR, MATERIALS, DESIGN COST ETC EVEN |
| | IF *ANY* IS OWNER SUPPLIED SHALL BE INCLUDED. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |