Text |
| 2007-09-24 10:52:32 | DENIED 3RD TIME |
| | REFERENCE: |
| | ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. NOTE: AS STATED ON PREVIOUS REVIEWS: |
| | PLEASE INCLUDE THE RELEVENT CODES AS ADOPTED BY FS |
| | 533.73. |
| | PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED |
| | ON PLANS. |
| | **FBC-2004 WITH 2006 REVISIONS, FUEL GAS. |
| | |
| | 2. PLEASE REFERENCE THE ELECTRICAL COMMENT #2 ON FIRM |
| | CHANGE AND TITLE BLOCK INFORMATION. |
| | |
| | 3. 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | |
| | 4. SHEET A-1 AND PE-1 INDICATE GENERATOR AS EXISTING, |
| | SSHEET PE-1 EXISTING GAS RISER INDICATES NEW GENERATOR. |
| | THIS IS CONFUSING, PLEASE CORRELATE THE PLANS ON THE |
| | RESUBMITTAL. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 5. SHEET PE-1 GAS RISER THE PRESSURE REGULATOR VALVE |
| | TO THE GENERATOR PER FBC-2004 FUEL GAS, SECTION 409.4 |
| | MP REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 6. SHEET PE-1 GAS RISER: WHAT IS THE PURPOSE OF THE |
| | MECHANICAL SHUT OFF VALVE LOCATED BETWEEN THE GAS METER |
| | AND GENERATOR? THIS IS NOT REQUIRED, PLEASE DELETE THIS |
| | ON THE RESUBMITTAL. |
| | |
| | 7. SHEET PE-1 GAS RISER: SHOW TYPE OF PIPING MATERIAL |
| | BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | NOTE: THE PIPING MATERIAL IS NOT INDICATED, PLEASE DO |
| | THIS ON THE RESUBMITTAL. |
| | |
| | 8. SHEET PE-1 PLUMBING NOTES: NOTE #1 PLEASE DELETE |
| | THE FOLLOWING "STANDARD PLUMBING CODE, CHAPTER 46" AND |
| | ADD IN ITS PLACE THE FOLLOWING "FBC-2004 WITH 2006 |
| | REVISIONS, FUEL GAS". |
| | |
| | 9. SHEET PE-1 PLUMBING NOTES: NOTE #3 PLEASE DELETE |
| | AND ADD IN ITS PLACE THE FOLLOWING PER FBC-2004 W/2006 |
| | REV. SECTION 404.8.2 PROTECTIVE COATINGS AND WRAPPINGS. |
| | PIPE PROTECTIVE COATINGS AND WRAPPINGS SHALL BE |
| | APPROVED FOR THE APPLICATION AND SHALL BE FACTORY |
| | APPLIED. EXCEPTION: WHERE INSTALLED IN ACCORDANCE WITH |
| | THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, FIELD |
| | APPLICATION OF COATINGS AND WRAPPINGS SHALL BE |
| | PERMITTED FOR PIPE NIPPLES, FITTINGS AND LOCATIONS |
| | WHERE THE FACTORY COATING OR WRAPPING HAS BEEN DAMAGED |
| | OR NECESSARILY REMOVED AT JOINTS. |
| | |
| | 10. SHEET PE-1 PLUMBING NOTES: NOTE #5 PLEASE DELETE |
| | THE FOLLOWING "402(1)" THIS IS FROM THE 2001 CODE WHICH |
| | IS THE WRONG CODE CYCLE. THE CORRECT TABLE FROM THE |
| | FBC-2004 W/2006 REV. IS 402.4(2). PLEASE CORRECT THIS |
| | ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK |
| | ON THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR |
| | REFERENCE FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |