Plan Review Notes
Plan Review Notes For Permit 07040466
Permit Number 07040466
Review Stop G
Sequence Number 3
Notes
Date Text
2007-09-24 10:52:32DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: AS STATED ON PREVIOUS REVIEWS:
 PLEASE INCLUDE THE RELEVENT CODES AS ADOPTED BY FS
 533.73.
 PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED
 ON PLANS.
 **FBC-2004 WITH 2006 REVISIONS, FUEL GAS.
  
 2. PLEASE REFERENCE THE ELECTRICAL COMMENT #2 ON FIRM
 CHANGE AND TITLE BLOCK INFORMATION.
  
 3. 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 4. SHEET A-1 AND PE-1 INDICATE GENERATOR AS EXISTING,
 SSHEET PE-1 EXISTING GAS RISER INDICATES NEW GENERATOR.
 THIS IS CONFUSING, PLEASE CORRELATE THE PLANS ON THE
 RESUBMITTAL. PER FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 5. SHEET PE-1 GAS RISER THE PRESSURE REGULATOR VALVE
 TO THE GENERATOR PER FBC-2004 FUEL GAS, SECTION 409.4
 MP REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 6. SHEET PE-1 GAS RISER: WHAT IS THE PURPOSE OF THE
 MECHANICAL SHUT OFF VALVE LOCATED BETWEEN THE GAS METER
 AND GENERATOR? THIS IS NOT REQUIRED, PLEASE DELETE THIS
 ON THE RESUBMITTAL.
  
 7. SHEET PE-1 GAS RISER: SHOW TYPE OF PIPING MATERIAL
 BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 NOTE: THE PIPING MATERIAL IS NOT INDICATED, PLEASE DO
 THIS ON THE RESUBMITTAL.
  
 8. SHEET PE-1 PLUMBING NOTES: NOTE #1 PLEASE DELETE
 THE FOLLOWING "STANDARD PLUMBING CODE, CHAPTER 46" AND
 ADD IN ITS PLACE THE FOLLOWING "FBC-2004 WITH 2006
 REVISIONS, FUEL GAS".
  
 9. SHEET PE-1 PLUMBING NOTES: NOTE #3 PLEASE DELETE
 AND ADD IN ITS PLACE THE FOLLOWING PER FBC-2004 W/2006
 REV. SECTION 404.8.2 PROTECTIVE COATINGS AND WRAPPINGS.
 PIPE PROTECTIVE COATINGS AND WRAPPINGS SHALL BE
 APPROVED FOR THE APPLICATION AND SHALL BE FACTORY
 APPLIED. EXCEPTION: WHERE INSTALLED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, FIELD
 APPLICATION OF COATINGS AND WRAPPINGS SHALL BE
 PERMITTED FOR PIPE NIPPLES, FITTINGS AND LOCATIONS
 WHERE THE FACTORY COATING OR WRAPPING HAS BEEN DAMAGED
 OR NECESSARILY REMOVED AT JOINTS.
  
 10. SHEET PE-1 PLUMBING NOTES: NOTE #5 PLEASE DELETE
 THE FOLLOWING "402(1)" THIS IS FROM THE 2001 CODE WHICH
 IS THE WRONG CODE CYCLE. THE CORRECT TABLE FROM THE
 FBC-2004 W/2006 REV. IS 402.4(2). PLEASE CORRECT THIS
 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER