Plan Review Notes
Plan Review Notes For Permit 07040466
Permit Number 07040466
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-18 15:55:15 
 ** DENIED 3RD TIME **
  
  
 ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 COMMENTS DUE TO INFORMATION OR CHANGES MADE TO PLANS.
 ** PLEASE SEE THE ELECTRICAL RISER AND PLANS HAVE BEEN
 COMPLETELY REVISED WITH SOMETHING DIFFERENT THAN SHOWN
 ON PREVIOUS PLANS.
  
 1) NOTE: AS STATED ON PREVIOUS REVIEWS: PLEASE INCLUDE
 THE RELEVANT CODES AS ADOPTED BY FS 553.73.
 PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
 ** PLEASE SEE CODES FROM OTHER TRADES.
 ** PLEASE KNOW THAT THE *LATEST EDITION* IS NOT
 SUFFICIENT.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS HAVE NOW BEEN
 CHANGED TO LIST A NEW FIRM. PLEASE SEE THERE ARE TWO
 NEW SETS. ONE SET DOES NOT CONTAIN ANY SIGNATURE, DATE
 OR SEAL ON SHEET A-1 AND THE OTHER SET FOR SHEET A-1
 CONTAINS A RAISED/EMBOSSED SEAL OVER A *PHOTO-COPIED*
 SIGNATURE AND DATE.
 PLEASE SEE FS 481.221 AS THIS REQUIRES AND ORIGINAL
 DATE AND SIGNATURE BY THE DESIGN PROFESSIONAL.
 ** PLANS WILL BE RETAINED BY THIS OFFICE FOR POSSIBLE
 REVIEW BY THE FLORIDA BOARD OF ARCHITECTS AND STATE
 LEGAL COUNSEL TO THE BOARD.
  
 3) NOTE: PLEASE SEE THE PLANS ON SHEET A-1 NOW CALL FOR
 THE GENERATOR BEING AS EXISTING! HOW IS THIS POSSIBLE
 WHEN THE PERMIT APPLICATION IS TO INSTALL THIS NEW
 UNIT? A FIELD INSPECTION MAY BE PERFORMED TO VERIFY IF
 THE INSTALLATION HAS TAKEN PLACE.
  
 4) NOTE: PLEASE CORRELATE PLANS. PLEASE SEE SHEET PE-1
 WHICH INDICATE A 4INCH CONDUIT AND 250MCM FOR
 CONDUCTORS YET THE ELECTRICAL RISER SHOWS 4-3/0*S.
 PLEASE SEE 310.16, 240.4 ETC.
 PLEASE SEE THE CONDUCTORS ON RISER ARE NOT OF
 SUFFICIENT SIZE BASED ON THE OVER CURRENT PROTECTION
 WHICH IS INDICATED ON THE GENERATOR SPECS SHEETS. THIS
 IS BEING SHOWN AS 300AMP.
  
 5) NOTE: PLEASE SEE RISER SHOWS THE BREAKER WHICH IS
 SUPPOSEDLYTHE EXISTING PANEL *A* AS 200AMPS. AS THE
 RISER DOES NOT INDICATE THE SIZE OF THIS EXISTING
 PANEL, THIS CAN NOT BE REVIEWED. THIS SEEMS INDICATE
 THIS PANEL BASED ON THE CONDUCTOR SIZES AND THE OVER
 CURRENT PROTECTION LISTED AS A 200AMP RATED PANEL. MAY
 NOT FEED A 200AMP PANEL WITH A 300AMP BREAKER. PREVIOUS
 RISER SHOWED THIS AS 400AMP PANEL.
 PLEASE INDICATE THE SIZES OF ALL EQUIPMENT ON RISER.
 PLEASE COMPLETE RISER WITH THE CORRECT OVER CURRENT
 PROTECTION DEVICES AND SIZES OF ALL EQUIPMENT TO
 COORDINATE WITH THE MINIMUM REQUIREMENTS OF THE 2005
 NEC/NFPA-70.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECT PER
 225.31-225.39
  
 7) NOTE: PLEASE SUBMIT THE MISSING MANUFACTURES
 SPECS/CUT SHEETS FOR THE NEW TRANSFER SWITCH. 110.3,
 90.7.
  
 8) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK INCLUDING ALL LABOR, EQUIPMENT, MATERIALS; DESIGN
 COST ETC SHALL MEET FBC 108.3.
 THIS IS REQUIRED EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
  
 9) NOTE: PLEASE CLARIFY HOW A 200AMP TRANSFER SWITCH IS
 BEING FED FROM A 300AMP BREAKER AND OVER CURRENT
 PROTECTION?
 NEC 2005
  
 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS IN ALL CONDUITS AFTER THE FIRST MEANS OF
 DISCONNECT OF SERVICE MAIN.
 250.110, 250.122, 250.24 ETC
  
 11) NOTE: PLEASE SUBMIT INTENDED LOADS AND LOAD SUMMARY
 PER NEC 220, 408.4
  
 12 NOTE: PLEASE SEE AS REQUESTED IN THE PREVIOUS REVIEW
 PLEASE SUBMIT TWO SETS OF COMPLETE PLANS INCLUDING ALL
 SPECIFICATIONS, ETC. PLEASE SEE SOME OF THE SHEETS ARE
 STILL ATTACHED TO OLD PLANS ETC.
 FBC 106.1.2, 106.1.3., 106.3.5.1.2
  
 ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED FOR
 REVIEW, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN ONLY
 BE BASED ON THE PLANS AND DOCUMENTS SUBMITTED.
  
  
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-18 14:49:28** REMOVED FROM INCOMING DUE TO DATED ORDER OF PLANS
 WHICH ELECTRICAL REVIEW IS UP TO.