| 2007-09-18 15:55:15 | |
| | ** DENIED 3RD TIME ** |
| | |
| | |
| | ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW |
| | COMMENTS DUE TO INFORMATION OR CHANGES MADE TO PLANS. |
| | ** PLEASE SEE THE ELECTRICAL RISER AND PLANS HAVE BEEN |
| | COMPLETELY REVISED WITH SOMETHING DIFFERENT THAN SHOWN |
| | ON PREVIOUS PLANS. |
| | |
| | 1) NOTE: AS STATED ON PREVIOUS REVIEWS: PLEASE INCLUDE |
| | THE RELEVANT CODES AS ADOPTED BY FS 553.73. |
| | PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED |
| | ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | ** PLEASE SEE CODES FROM OTHER TRADES. |
| | ** PLEASE KNOW THAT THE *LATEST EDITION* IS NOT |
| | SUFFICIENT. |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCKS HAVE NOW BEEN |
| | CHANGED TO LIST A NEW FIRM. PLEASE SEE THERE ARE TWO |
| | NEW SETS. ONE SET DOES NOT CONTAIN ANY SIGNATURE, DATE |
| | OR SEAL ON SHEET A-1 AND THE OTHER SET FOR SHEET A-1 |
| | CONTAINS A RAISED/EMBOSSED SEAL OVER A *PHOTO-COPIED* |
| | SIGNATURE AND DATE. |
| | PLEASE SEE FS 481.221 AS THIS REQUIRES AND ORIGINAL |
| | DATE AND SIGNATURE BY THE DESIGN PROFESSIONAL. |
| | ** PLANS WILL BE RETAINED BY THIS OFFICE FOR POSSIBLE |
| | REVIEW BY THE FLORIDA BOARD OF ARCHITECTS AND STATE |
| | LEGAL COUNSEL TO THE BOARD. |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS ON SHEET A-1 NOW CALL FOR |
| | THE GENERATOR BEING AS EXISTING! HOW IS THIS POSSIBLE |
| | WHEN THE PERMIT APPLICATION IS TO INSTALL THIS NEW |
| | UNIT? A FIELD INSPECTION MAY BE PERFORMED TO VERIFY IF |
| | THE INSTALLATION HAS TAKEN PLACE. |
| | |
| | 4) NOTE: PLEASE CORRELATE PLANS. PLEASE SEE SHEET PE-1 |
| | WHICH INDICATE A 4INCH CONDUIT AND 250MCM FOR |
| | CONDUCTORS YET THE ELECTRICAL RISER SHOWS 4-3/0*S. |
| | PLEASE SEE 310.16, 240.4 ETC. |
| | PLEASE SEE THE CONDUCTORS ON RISER ARE NOT OF |
| | SUFFICIENT SIZE BASED ON THE OVER CURRENT PROTECTION |
| | WHICH IS INDICATED ON THE GENERATOR SPECS SHEETS. THIS |
| | IS BEING SHOWN AS 300AMP. |
| | |
| | 5) NOTE: PLEASE SEE RISER SHOWS THE BREAKER WHICH IS |
| | SUPPOSEDLYTHE EXISTING PANEL *A* AS 200AMPS. AS THE |
| | RISER DOES NOT INDICATE THE SIZE OF THIS EXISTING |
| | PANEL, THIS CAN NOT BE REVIEWED. THIS SEEMS INDICATE |
| | THIS PANEL BASED ON THE CONDUCTOR SIZES AND THE OVER |
| | CURRENT PROTECTION LISTED AS A 200AMP RATED PANEL. MAY |
| | NOT FEED A 200AMP PANEL WITH A 300AMP BREAKER. PREVIOUS |
| | RISER SHOWED THIS AS 400AMP PANEL. |
| | PLEASE INDICATE THE SIZES OF ALL EQUIPMENT ON RISER. |
| | PLEASE COMPLETE RISER WITH THE CORRECT OVER CURRENT |
| | PROTECTION DEVICES AND SIZES OF ALL EQUIPMENT TO |
| | COORDINATE WITH THE MINIMUM REQUIREMENTS OF THE 2005 |
| | NEC/NFPA-70. |
| | |
| | 6) NOTE: PLEASE SEE MISSING DISCONNECT PER |
| | 225.31-225.39 |
| | |
| | 7) NOTE: PLEASE SUBMIT THE MISSING MANUFACTURES |
| | SPECS/CUT SHEETS FOR THE NEW TRANSFER SWITCH. 110.3, |
| | 90.7. |
| | |
| | 8) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK INCLUDING ALL LABOR, EQUIPMENT, MATERIALS; DESIGN |
| | COST ETC SHALL MEET FBC 108.3. |
| | THIS IS REQUIRED EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. |
| | |
| | 9) NOTE: PLEASE CLARIFY HOW A 200AMP TRANSFER SWITCH IS |
| | BEING FED FROM A 300AMP BREAKER AND OVER CURRENT |
| | PROTECTION? |
| | NEC 2005 |
| | |
| | 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTORS IN ALL CONDUITS AFTER THE FIRST MEANS OF |
| | DISCONNECT OF SERVICE MAIN. |
| | 250.110, 250.122, 250.24 ETC |
| | |
| | 11) NOTE: PLEASE SUBMIT INTENDED LOADS AND LOAD SUMMARY |
| | PER NEC 220, 408.4 |
| | |
| | 12 NOTE: PLEASE SEE AS REQUESTED IN THE PREVIOUS REVIEW |
| | PLEASE SUBMIT TWO SETS OF COMPLETE PLANS INCLUDING ALL |
| | SPECIFICATIONS, ETC. PLEASE SEE SOME OF THE SHEETS ARE |
| | STILL ATTACHED TO OLD PLANS ETC. |
| | FBC 106.1.2, 106.1.3., 106.3.5.1.2 |
| | |
| | ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED FOR |
| | REVIEW, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN ONLY |
| | BE BASED ON THE PLANS AND DOCUMENTS SUBMITTED. |
| | |
| | |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-18 14:49:28 | ** REMOVED FROM INCOMING DUE TO DATED ORDER OF PLANS |
| | WHICH ELECTRICAL REVIEW IS UP TO. |