2007-09-25 12:39:28 
 BUILDING PLAN REVIEW
 PERMIT:07040466
 ADD: 1572 PBL BLVD
 CONT:KEDECO ENTERPRISES INC.
 TEL: (561)712-9733
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004
 **NEW** THIS INFORMATION IS REQUIRED ON THE DRAWINGS.
 SHEET A- 1 IS NOT SIGNED OR SEALED.
 F.A.C. 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
  
 3)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER 61G15-23.002 (2)
 FAC. THE PERSON FROM HILLMAN ENGINEERING INC. WHO IS
 RESPONSIBLE FOR THE DRAWINGS NEEDS TO SIGN AND SEAL THE
 DRAWINGS.NOTE: THESE DRAWINGS ARE NOT SHOP DRAWINGS AS
 INDICATED.
  
 4)OK
  
 PARTIALLY CORRECT******
 5)THE NEW WALL SECTION DRAWINGS REQUIRE MORE
 INFORMATION. THE DRAWINGS SHALL BE SIGN/SEAL AND DATED
 BY THE DESIGN PROFESSIONAL. STATE THE BUILDING CODE
 UNDER WHICH THE DRAWINGS ARE DESIGNED AND THE WIND
 INFORMATION PER FBC. SECTION 1603.1.4 **NO RESPONSE NOT
 ADDRESSED**
 **NEW** THE INFORMATION BELOW SHALL BE INDICATED ON THE
 DRAWINGS.
 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION
 RELATED TO WIND SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1) - BASIC WIND SPEED, MPH
 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3) - WIND EXPOSURE
 4) - INTERNAL PRESSURE COEFFICIENT,
 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES
 IN TERMS OF PSF.
  
 NOTE:THE DRAWINGS ARE NOT TO THE SCALE INDICATED. THE
 DRAWINGS NEEDS TO MATCH THE SCALE INDICATED.
 **NO RESPONSE NOT ADDRESS**
  
 6)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 SEE COMMENTS FROM THE OTHER TRADES. IS THE GENERATOR
 EXISTING OR NEW? CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected].