| | BUILDING PLAN REVIEW |
| | PERMIT:07040466 |
| | ADD: 1572 PBL BLVD |
| | CONT:KEDECO ENTERPRISES INC. |
| | TEL: (561)712-9733 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 3RD |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| | PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA |
| | STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND |
| | DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC |
| | 2004 |
| | **NEW** THIS INFORMATION IS REQUIRED ON THE DRAWINGS. |
| | SHEET A- 1 IS NOT SIGNED OR SEALED. |
| | F.A.C. 61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | |
| | 3)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED |
| | ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND |
| | LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| | OF AUTHORIZATION #ON EACH SHEET PER 61G15-23.002 (2) |
| | FAC. THE PERSON FROM HILLMAN ENGINEERING INC. WHO IS |
| | RESPONSIBLE FOR THE DRAWINGS NEEDS TO SIGN AND SEAL THE |
| | DRAWINGS.NOTE: THESE DRAWINGS ARE NOT SHOP DRAWINGS AS |
| | INDICATED. |
| | |
| | 4)OK |
| | |
| | PARTIALLY CORRECT****** |
| | 5)THE NEW WALL SECTION DRAWINGS REQUIRE MORE |
| | INFORMATION. THE DRAWINGS SHALL BE SIGN/SEAL AND DATED |
| | BY THE DESIGN PROFESSIONAL. STATE THE BUILDING CODE |
| | UNDER WHICH THE DRAWINGS ARE DESIGNED AND THE WIND |
| | INFORMATION PER FBC. SECTION 1603.1.4 **NO RESPONSE NOT |
| | ADDRESSED** |
| | **NEW** THE INFORMATION BELOW SHALL BE INDICATED ON THE |
| | DRAWINGS. |
| | 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION |
| | RELATED TO WIND SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1) - BASIC WIND SPEED, MPH |
| | 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY |
| | 3) - WIND EXPOSURE |
| | 4) - INTERNAL PRESSURE COEFFICIENT, |
| | 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF. |
| | |
| | NOTE:THE DRAWINGS ARE NOT TO THE SCALE INDICATED. THE |
| | DRAWINGS NEEDS TO MATCH THE SCALE INDICATED. |
| | **NO RESPONSE NOT ADDRESS** |
| | |
| | 6)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | SEE COMMENTS FROM THE OTHER TRADES. IS THE GENERATOR |
| | EXISTING OR NEW? CLARIFY. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | [email protected]. |