2007-07-26 11:55:56----------------DENIED-------------------
  
 FBC 4002 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 NFPA 37-02
  
 1. SHOW ON SITE PLAN THE DISTANCE OF GENERATOR FROM
 PROPERTY LINES AND ADJACENT BUILDINGS.
  
 2. GENERATOR SHALL BE INSTALLED PER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, WHICH WERE NOT PROVIDED.
 PROVIDE INFORMATION SUCH AS REQUIRED CLEARANCE FROM
 WALLS/BUILDINGS FOR SERVICE, MAINTENANCE, AIRFLOW FOR
 COOLING AND COMBUSTION.
  
 3. SHOW WEATHERPROOF ENCLOSURE AND ATTACHMENT TO SLAB
 TO BE DESIGNED FOR MIN. 140 MPH WIND ZONE PER FBC,M
 301.13 AND FBC CH. 16
  