| 2007-07-31 11:06:09 | DENIED; |
| | SAME COMMENTS AS LAST REVIEW; |
| | 1. GAS PERMIT REQUIRED. GAS CONTRACTOR TO SUBMIT PLANS |
| | WITH PERMIT APPLICATION. |
| | ******* IMPORTANT INFORMATION******* |
| | AS OF 8/25/06 GENERATOR PERMIT APPLICATIONS |
| | SHALL NOT BE ACCEPTED UNLESS THE ELECTRIC AND GAS |
| | INFORMATION IS TO BE SUBMITED AT THE SAME TIME. ( NO |
| | GAS APPLICATION OR PLAN HAS BEEN SUBMITED). |
| | 2.SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | 3.SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 4.TYPE OF GAS, (LP OR NATURAL) |
| | 5.BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | 6.SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 8.SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | 9.INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | GAS PLAN REVIEW BY; |
| | JOHN LEECH |
| | 805-6695 |