| Plan Review Notes For Permit 07040466 |
| Permit Number |
07040466 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-31 10:20:38 | ***DENIED*** | | | | | | PLEASE NOTE THAT SOME COMMENTS FROM PREVIOUS REVIEW | | | NEED TO BE ADDRESSED. | | | | | | 1) OK | | | | | | 2) NFPA 110, STANDARD FOR EMERGENCY AND STAND BY POWER | | | SYSTEMS SHALL BE COMPLIED WITH. PLEASE ADD TO PLANS. | | | | | | 3) THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO PROPERTY OR VICINITY | | | INCLUDING STREETS, ROADS, FIRELANES ETC. PLEASE | | | RESPOND | | | | | | 4) DEPENDANT UPON LOCATION OF THE EQUIPMENT, SAFEGUARDS | | | AGAINST MECHANICAL DAMAGE MAY BE REQUIRED. PLEASE | | | ADVISE | | | | | | 5) OK | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|