| 2007-07-06 10:19:03 | 2007-07-06 10:19:03 |
| | ** UNSAT 2ND REVIEW ** |
| | |
| | **PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | ** PLEASE SEE THERE ARE NEW NOTES DUE TO NEW A SHEETS |
| | SUBMITTED AND REPEAT COMMENTS NOTE. |
| | |
| | |
| | 1) NOTE: SAME NOTE FROM PREVIOUS REVIEW. |
| | PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE |
| | THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC |
| | FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE |
| | ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL |
| | TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-110 |
| | ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER |
| | TRADES. |
| | |
| | 2) NOTE: SAME NOTE FROM PREVIOUS REVIEW: HOWEVER PLEASE |
| | ALSO SEE NEW NOTES BELOW WITH RESPECT TO THE NEW |
| | A-SHEETS. |
| | PLEASE SEE BUILDING REVIEW COMMENTS AS THE ENGINEERING |
| | SHEETS SUBMITTED ARE NOT SIGNED, DATED OR SEALED AS |
| | REQUIRED PER FAC 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: SAME NOTE AS PREVIOUS REVIEW. |
| | PLEASE SEE THE ELECTRICAL SHEETS EVEN WHEN FALLING |
| | UNDER THE EXCEPTION OF FS 471.003 STILL REQUIRES THE |
| | PRINTED NAME AND SIGNATURE OF THE DESIGN PROFESSIONAL |
| | WHICH IN THIS CASE IS THE ELECTRICAL CONTRACTOR. |
| | |
| | 4) NOTE: SAME NOTE AS PREVIOUS PLANS. |
| | PLEASE KNOW THAT NO HAND DRAWN PEN OR PENCIL MAY BE |
| | DRAWN ON PLANS WHICH ARE SIGNED AND SEALED BY A DESIGN |
| | PROFESSIONAL. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. (SEE SITE PLANS. |
| | PLEASE ALSO SEE THE SHEETS FOR SITE CONTAIN A RAISED |
| | SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT |
| | PERMITTED PER FS 472.025 |
| | |
| | 5) NOTE: SAME NOTE AS PREVIOUS PLANS. |
| | PLEASE SEE THE RISER IS NOT COMPLETE AT THIS TIME. |
| | PLEASE COMPLETE WITH ALL EQUIPMENT, MTS, ATS ETC. NO |
| | TRANSFER DEVICES ARE SHOWN EVEN IF THEY ARE EXISTING. |
| | PLEASE BE SURE TO DELINEATE WHAT IS EXISTING AND NEW. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE |
| | TRANSFER DEVICE(EVEN IF EXISTING). THIS RECORD SET OF |
| | PLANS NEEDS TO SHOW CODE COMPLIANCE. |
| | PLEASE KNOW THAT VERIFICATION FOR THE REQUIRED |
| | DISCONNECTING MEANS CAN NOT BE VERIFIED AT THIS TIME. |
| | 110.3, 90.7, FBC 106.1.2 |
| | |
| | 6) NOTE: SAME NOTE AS PREVIOUS REVIEW. |
| | PLEASE SEE FEEDERS ARE NOT RATED FOR 150AMPS PER THE 75 |
| | DEGREE COLUMN PER 310.16, 110.14. PLEASE ADJUST |
| | FEEDERS. |
| | |
| | 7) NOTE: SAME NOTE AS PREVIOUS REVIEW. |
| | PLEASE SEE 250.122 AS THE EQUIPMENT GROUNDING |
| | CONDUCTOR IS NOT LARGER ENOUGH. (#4 MIN) |
| | |
| | 8) NOTE: SAME NOTE AS PREVIOUS REVIEW. |
| | PLEASE SEE 310.4 AS PARALLEL CONDUCTORS MAY NOT BE RUN |
| | SMALLER THAN 1/0. |
| | |
| | 9) NOTE: SAME NOTE AS PREVIOUS REVIEW. |
| | PLEASE SUBMIT LOAD CALCULATIONS FOR INTENDED LOADS. |
| | 702.5, 220 |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: SAME NOTE AS PREVIOUS REVIEW. |
| | PLEASE SEE PLUMBING REVIEW COMMENTS FOR MISSING |
| | REQUIRED GAS RISER. |
| | |
| | |
| | ** NEW NOTES** |
| | |
| | 11) NOTE: PLEASE SEE THE NEW A-SHEETS WHICH ARE MISSING |
| | INFORMATION REQUIRED PER FAC 61G1-16.004, FS 481.219. |
| | PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER |
| | OF ARCHITECT AND MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER. IT WAS LOCATED ON THE STATE WEBSITE THAT THE |
| | APPLICATION HAS BEEN MADE FOR THE STATE LICENSE HOWEVER |
| | APPLICATION FOR LICENSE IN LIEU OF THE ACTUAL REQUIRED |
| | LICENSE ON SHEETS CAN NOT BE ACCEPTED. |
| | PLEASE SEE WE HAVE ATTACHED THIS SHEET PRINTED THE |
| | |
| | 12) NOTE: PLEASE SEE THE APPLIED FOR VALUE FOR THE |
| | COMPLETE SCOPE OF WORK SHOWN AND AS APPLIED FOR IS LOW. |
| | PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR, MATERIALS |
| | , EQUIPMENT, DESIGN COST, ETC EVEN IF ANY OF THESE |
| | ITEMS ARE OWNER SUPPLIED. |
| | PLEASE SEE FBC 108.3. |
| | PLEASE KNOW AN ADJUSTMENT MAY BE MADE BY THIS OFFICE |
| | USING ADOPTED REFERENCES TO THE FBC IF THE VALUE IS NOT |
| | ADJUSTED BY THE CONTRACTOR. |
| | |
| | 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY AN NOTICE GIVEN AT THIS TIME. |
| | |
| | ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED |
| | INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE |
| | COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-06 09:11:25 | 2007-07-06 09:11:25 |
| | PLANS REMOVED FROM INCOMING. WILL RETURN TO INCOMING |
| | WATING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS |
| | COMPLETED. |