Plan Review Notes
Plan Review Notes For Permit 07040466
Permit Number 07040466
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-06 10:19:032007-07-06 10:19:03
 ** UNSAT 2ND REVIEW **
  
 **PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 ** PLEASE SEE THERE ARE NEW NOTES DUE TO NEW A SHEETS
 SUBMITTED AND REPEAT COMMENTS NOTE.
  
  
 1) NOTE: SAME NOTE FROM PREVIOUS REVIEW.
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
 ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER
 TRADES.
  
 2) NOTE: SAME NOTE FROM PREVIOUS REVIEW: HOWEVER PLEASE
 ALSO SEE NEW NOTES BELOW WITH RESPECT TO THE NEW
 A-SHEETS.
 PLEASE SEE BUILDING REVIEW COMMENTS AS THE ENGINEERING
 SHEETS SUBMITTED ARE NOT SIGNED, DATED OR SEALED AS
 REQUIRED PER FAC 61G15-23.002, FS 471.025
  
 3) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE THE ELECTRICAL SHEETS EVEN WHEN FALLING
 UNDER THE EXCEPTION OF FS 471.003 STILL REQUIRES THE
 PRINTED NAME AND SIGNATURE OF THE DESIGN PROFESSIONAL
 WHICH IN THIS CASE IS THE ELECTRICAL CONTRACTOR.
  
 4) NOTE: SAME NOTE AS PREVIOUS PLANS.
 PLEASE KNOW THAT NO HAND DRAWN PEN OR PENCIL MAY BE
 DRAWN ON PLANS WHICH ARE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES. (SEE SITE PLANS.
 PLEASE ALSO SEE THE SHEETS FOR SITE CONTAIN A RAISED
 SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT
 PERMITTED PER FS 472.025
  
 5) NOTE: SAME NOTE AS PREVIOUS PLANS.
 PLEASE SEE THE RISER IS NOT COMPLETE AT THIS TIME.
 PLEASE COMPLETE WITH ALL EQUIPMENT, MTS, ATS ETC. NO
 TRANSFER DEVICES ARE SHOWN EVEN IF THEY ARE EXISTING.
 PLEASE BE SURE TO DELINEATE WHAT IS EXISTING AND NEW.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE
 TRANSFER DEVICE(EVEN IF EXISTING). THIS RECORD SET OF
 PLANS NEEDS TO SHOW CODE COMPLIANCE.
 PLEASE KNOW THAT VERIFICATION FOR THE REQUIRED
 DISCONNECTING MEANS CAN NOT BE VERIFIED AT THIS TIME.
 110.3, 90.7, FBC 106.1.2
  
 6) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE FEEDERS ARE NOT RATED FOR 150AMPS PER THE 75
 DEGREE COLUMN PER 310.16, 110.14. PLEASE ADJUST
 FEEDERS.
  
 7) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE 250.122 AS THE EQUIPMENT GROUNDING
 CONDUCTOR IS NOT LARGER ENOUGH. (#4 MIN)
  
 8) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE 310.4 AS PARALLEL CONDUCTORS MAY NOT BE RUN
 SMALLER THAN 1/0.
  
 9) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SUBMIT LOAD CALCULATIONS FOR INTENDED LOADS.
 702.5, 220
 FBC 106.1.2
  
 10) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE PLUMBING REVIEW COMMENTS FOR MISSING
 REQUIRED GAS RISER.
  
  
 ** NEW NOTES**
  
 11) NOTE: PLEASE SEE THE NEW A-SHEETS WHICH ARE MISSING
 INFORMATION REQUIRED PER FAC 61G1-16.004, FS 481.219.
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 OF ARCHITECT AND MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. IT WAS LOCATED ON THE STATE WEBSITE THAT THE
 APPLICATION HAS BEEN MADE FOR THE STATE LICENSE HOWEVER
 APPLICATION FOR LICENSE IN LIEU OF THE ACTUAL REQUIRED
 LICENSE ON SHEETS CAN NOT BE ACCEPTED.
 PLEASE SEE WE HAVE ATTACHED THIS SHEET PRINTED THE
  
 12) NOTE: PLEASE SEE THE APPLIED FOR VALUE FOR THE
 COMPLETE SCOPE OF WORK SHOWN AND AS APPLIED FOR IS LOW.
 PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR, MATERIALS
 , EQUIPMENT, DESIGN COST, ETC EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED.
 PLEASE SEE FBC 108.3.
 PLEASE KNOW AN ADJUSTMENT MAY BE MADE BY THIS OFFICE
 USING ADOPTED REFERENCES TO THE FBC IF THE VALUE IS NOT
 ADJUSTED BY THE CONTRACTOR.
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY AN NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED
 INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE
 COMMENTS ON THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-06 09:11:252007-07-06 09:11:25
 PLANS REMOVED FROM INCOMING. WILL RETURN TO INCOMING
 WATING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS
 COMPLETED.