| 2007-06-04 09:14:04 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | CONTRACTOR INFORMATION |
| | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- |
| | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- |
| | TION. ALL GAS INSPECTIONS TO BE COMPLETE |
| | BEFORE FINAL GEN/COM INSPECTION. |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | 3. PLEASE INDICATE TYPE OF GAS, (LP OR NATURAL) ON GAS |
| | DRAWINGS. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI OR GREATER |
| | PLEASE SUBMIT MANUFACTURER SPECIFICATON SHEETS OF MP |
| | REGULATOR INDICATING THE MANUFACTURER'S NAME, MAXIMUM |
| | BTU LOAD CAPACITY AND SHOW A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY (NRTL). |
| | |
| | 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS ON FUTURE SUBMITTED GAS DRAWINGS. |
| | |
| | 9. NOTE: A GAS PERMIT CAN NOT BE ISSUED UNTIL A |
| | GEN/COM PERMIT APPLICATION HAS BEEN APPROVED BY ZONING |
| | FOR THE GENERATOR LOCATION. |
| | |
| | 10. NOTE: PLANS ARE NOT ACCEPTABLE PER FBC-2004 |
| | CHAPTER 1, SECTIONS 106.1.1 AND 106.1.3, PLEASE DO NOT |
| | MODIFY PLANS WITH PEN OR PENCIL ONCE PLANS HAVE BEEN |
| | SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. (SEE |
| | SUBMITTED SITE PLANS) |
| | |
| | END OF COMMENTS: |
| | |