| Plan Review Notes For Permit 07040466 |
| Permit Number |
07040466 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-08 14:35:04 | *****DENIED***** | | | | | | | | | 1.THE COMPLETE ADDRESS OF THE PROJECT SITE SHALL BE | | | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY | | | POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 110. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING STREETS, ROADS, FIRE | | | LANES) | | | | | | 4.DEPENDANT UPON LOCATION OF THE EQUIPMENT, | | | SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED | | | AND SHALL BE ILLUSTRATED. | | | | | | 5. CLEARLYIDENTIFY LOCATION OF GENERATOR WITH | | | RELATION TO BUILDING OPENINGS AND ILLUSTRATE | | | DISTANCES. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|