2007-06-08 14:35:04*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 110.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ROADS, FIRE
 LANES)
  
 4.DEPENDANT UPON LOCATION OF THE EQUIPMENT,
 SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED
 AND SHALL BE ILLUSTRATED.
  
 5. CLEARLYIDENTIFY LOCATION OF GENERATOR WITH
 RELATION TO BUILDING OPENINGS AND ILLUSTRATE
 DISTANCES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  