Plan Review Notes
Plan Review Notes For Permit 07040466
Permit Number 07040466
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-01 16:52:07** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
 ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AS THE
 ENGINEERING SHEETS SUBMITTED ARE NOT SIGNED, DATED OR
 SEALED AS REQUIRED PER FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE SEE THE ELECTRICAL SHEETS EVEN WHEN
 FALLING UNDER THE EXCEPTION OF FS 471.003 STILL
 REQUIRES THE PRINTED NAME AND SIGNATURE OF THE DESIGN
 PROFESSIONAL WHICH IN THIS CASE IS THE ELECTRICAL
 CONTRACTOR.
  
 4) NOTE: PLEASE KNOW THAT NO HAND DRAWN PEN OR PENCIL
 MAY BE DRAWN ON PLANS WHICH ARE SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES. (SEE SITE PLANS.
 PLEASE ALSO SEE THE SHEETS FOR SITE CONTAIN A RAISED
 SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT
 PERMITTED PER FS 472.025
  
 5) NOTE: PLEASE SEE THE RISER IS NOT COMPLETE AT THIS
 TIME. PLEASE COMPLETE WITH ALL EQUIPMENT, MTS, ATS
 ETC.
 NO TRANSFER DEVICES ARE SHOWN EVEN OF THEY ARE
 EXISTING.
 PLEASE BE SURE TO DELINEATE WHAT IS EXISTING AND NEW.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE
 TRANSFER DEVICE(EVEN IF EXISTING). THIS RECORD SET OF
 PLANS NEEDS TO SHOW CODE COMPLIANCE.
 PLEASE KNOW THAT VERIFICATION FOR THE REQUIRED
 DISCONNECTING MEANS CAN NOT BE VERIFIED AT THIS TIME.
 110.3, 90.7, FBC 106.1.2
  
 6) NOTE: PLEASE SEE FEEDERS ARE NOT RATED FOR 150AMPS
 PER THE 75 DEGREE COLUMN PER 310.16, 110.14. PLEASE
 ADJUST FEEDERS.
  
 7) NOTE: PLEASE SEE 250.122 AS THE EQUIPMENT GROUNDING
 CONDUCTOR IS NOT LARGER ENOUGH. (#4 MIN)
  
 8) NOTE: PLEASE SEE 310.4 AS PARALLEL CONDUCTORS MAY
 NOT BE RUN SMALLER THAN 1/0.
  
 9) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR INTENDED
 LOADS.
 702.5, 220
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE PLUMBING REVIEW COMMENTS FOR
 MISSING REQUIRED GAS RISER.
  
 ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED
 INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE
 COMMENTS ON THE FOLLOWING REVIEW.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-05-01 12:46:30REMOVED FROM INCOMING, IN ELEC FOR REVIEW. WILL RETURN
 TO INCOMING TABLE WAITING FOR COMM BOARD ONCE REVIEW IS
 COMPLETED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved