Plan Review Notes
Plan Review Notes For Permit 07040456
Permit Number 07040456
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-16 10:30:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE PLANS SPECIFY JOHNS MANVILLE FOR THE FLAT
 DECK.CHANGING THE PRODUCT REQUIRES A REVISION TO THE
 BUILDING PERMIT AS THE DESIGNER OF RECORD HAS SPECIFIED
 THE PRODUCT IN THE PLAN.
  
 2.)IF YOU ARE USING THE GAF AS PROPOSED WITH THIS
 PERMIT, INDICATE WHICH BASE SHEET FASTENER YOU ARE
 USING AS THE DIFFERENT OPTIONS HAVE DIFFERENT DESIGN
 PRESSURE LIMITATIONS.
  
 3.)THE ROOFING CONTRACTOR HAS SELECTED AN ASSEMBLY
 WHICH IS DIFFERENT FROM THE ASSEMBLY CHOSEN AT THE TIME
 OF PERMIT ISSUANCE FOR THE MASTER PERMIT, METAL ROOF.
 THE ASSEMBLY THE ROOF CONTRACTOR HAS SELECTED HAS A
 DESIGN PRESSURE LIMITATION OF -27.5, NOT COMPLIANT FOR
 ZONE 1 (REQUIRES -32.3).
  
 4.)ZONES 2 AND 3 REQUIRE -68.1 AS PER PLAN.SEE
 LIMITATION #1, PAGE 8.CALCULATIONS PREPARED BY AN
 ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT
 REQUIRED.
  
 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
  
  
  